Technical data
Table Of Contents
- Table of contents
- 1 Key to symbols and safety instructions
- 1.1 Explanation of symbols
- 1.2 Safety instructions
- 2 About the appliance
- 2.1 Designated use
- 2.2 EU Declaration of Conformity
- 2.3 Data plate
- 2.4 Standard delivery
- 2.5 Accessories
- 2.6 Tools, materials and miscellaneous parts
- 2.7 General information on energy use and heat production
- 2.8 Function description of the hybrid manager
- 2.9 Handling circuit boards
- 2.10 Refrigerant circuit
- 2.11 Combi boiler with serial buffer tank, bypass valve and unmixed heating circuit
- 2.12 System boiler with serial buffer tank, bypass valve and unmixed heating circuit
- 2.13 Combi boiler with serial buffer tank, bypass valve, unmixed heating circuit and independently controlled mixed heating circuit
- 2.14 System boiler with serial buffer tank, bypass valve, unmixed heating circuit and independently controlled mixed heating circuit
- 2.15 Overview of components
- 2.16 Dimensions
- 2.17 Technical Data
- 3 Regulations
- 4 Transport
- 5 Mounting and installation
- 5.1 Preparing for installation
- 5.2 System component configuration
- 5.3 Pre-installing pipes
- 5.4 Mounting the hybrid manager
- 5.5 Installing the external unit
- 5.6 Installing the refrigerant circuit
- 5.7 Making the electrical connection
- 5.8 Installing the outside temperature sensor
- 5.9 Setting the DIP switches of the external unit
- 6 Commissioning
- 6.1 Before commissioning
- 6.2 Commissioning the system for the first time
- 6.2.1 Providing the external unit with a power supply ahead of commissioning
- 6.2.2 providing the external unit with a power supply during commissioning
- 6.2.3 Connecting the CANBUS cable to the hybrid manager unit
- 6.2.4 Making the power supply connection
- 6.2.5 Switching on the hybrid system
- 6.2.6 Connecting the programming unit to the hybrid control module
- 6.2.7 Connecting the heat source to the hybrid manager
- 6.2.8 Communication error from External unit on initial power ON of External Unit and Hybrid Manager
- 6.2.9 Adjusting the Hybrid manager circulating pump in the hybrid manager
- 6.2.10 System with series buffer tank
- 6.2.11 Venting the hybrid manager
- 6.2.12 Setting the bypass valve
- 6.2.13 Setting parameters for optimising energy use and costs of the hybrid system
- 6.2.14 Explanation of the parameters for energy and cost optimization of the hybrid system (control strategy)
- 6.2.15 Control Strategy: Option CO2 Optimised and co2 :cost mix
- 6.2.16 Control Strategy: Co2 optimised (environmental factors)
- 6.2.17 Control Strategy: CO2: Cost mix
- 6.2.18 Control Strategy: Option changeover temperature
- 6.2.19 Control Strategy: Cost optimised
- 6.2.20 Control strategy: hydraulic connection
- 6.2.21 Control strategy: Delay time for boiler heating
- 6.2.22 Control strategy: Temperature diff for boiler switch ON
- 6.2.23 Setting parameters at the hybrid control module
- 6.2.24 Commissioning of the air to water heat pump at outside temperatures outside the standard operating range
- 6.2.25 Informing the customer and handing over the technical documents
- 7 Operation
- 8 Environmental protection/disposal
- 9 Inspection and maintenance
- 10 Faults
- 10.1 Faults that are not displayed
- 10.2 Displayed faults
- Overview of internal hybrid fault indicators locations
- 10.2.1 Fault displays on the hybrid control module
- 10.2.2 Check temperature sensor of hybrid manager
- 10.2.3 Faults of the FW200 programming unit
- 10.2.4 Fault display on the FW 200 weather-compensated controller at user level
- 10.2.5 Fault display on the rear of the hybrid manager
- 10.2.6 External unit faults
- 10.2.7 Check components
- 10.2.8 DC fan motors/check PCB
- 10.2.9 Check external unit temperature sensor
- 10.2.10 Check linear expansion valves (LEV)
- 11 Replace components
- 11.1 Pumping refrigerant back into the external unit
- 11.2 Removing the casing from the external unit
- 11.3 Replacing the fan motor
- 11.4 Replacing the PCB housing
- 11.5 Replacing PCBs
- 11.6 Replacing faulty temperature sensors TH3, TH6 or TH33
- 11.7 Replacing outside temperature sensor TH7
- 11.8 Replacing temperature sensors TH4 and TH32
- 11.9 Fitting and removing the linear expansion valve
- 11.10 Removing the transformer (ACL)
- 12 Filling the refrigerant circuit
- 13 Appendix
- 13.1 Cost weighting electricity price — gas price
- 13.2 System wiring (heatronic III boiler connections) with a bypass valve and one unmixed heating circuit
- 13.3 System wiring (CUS boiler connections) with a bypass valve and one unmixed heating circuit
- 13.4 Wiring to PCB in the external unit (heat pump)
- 13.5 Controller circuit board in external unit
- 13.6 Alternative pipe work lengths and T
- 14 General details
- 15 Assembly and installation report for the installer
- 16 Commissioning report for the commissioning engineer

COMMISSIONING
6 720 803 687 (2012/11)44
6.2.23 SETTING PARAMETERS AT THE HYBRID CONTROL MODULE
Fig. 51 Control module of the hybrid manager
[1] Fuse, 5 AT, ceramic, filled with sand
[2] Spare fuse
[3] Service key connection
[4] Rotary selector: turn to scroll, push to select
[5] Display
[6] Back button
Display [5] shows the current status/display code or parameter list. This
can be recognised by the letters on the right hand side of the display.
• “c”: Parameter list
• “e”: Status/display code
▶ With the “Back button”, change between the current status/display
code and parameter list.
▶ Scroll through the parameter list with the “Rotary selector”.
▶ Push “Rotary selector” to select any parameter.
The selected parameter begins to flash.
▶ Set the required value by turning the “Rotary selector”.
▶ Push “Rotary selector” to confirm and save the new parameter setting.
6 720 646 970-36.2ITL
1
2
3
4
5 6
Display
code Description Unit
Standard
setting Input range
Aa Setting the hydraulic
system
— 0 0 = In series
1 = In parallel (not
possible with this
system)
This determines the function of the pump in the Hybrid
Manager.
0= the pump provides water circulation around the central
heating circuit(s) - used for all hydraulics described in this
document,
1= the pump does not provide water circulation around the
central heating circuit(s), for this type of system each
heating circuit has its own pump.
Ab Heat source delay min 20 5 - 120 The HTH (high temperature heat source) delay time given
to the boiler if; (The required system flow temperature –
the actual system flow temperature) is equal to or less than
the set Delta T.
Ac Heat source delay
temperature
K 3 1 - 99 The delta temperature used by the delay timer.
The temperature difference between the required system
flow temperature and the actual system flow temperature
that will activate the delay time.
A5 External unit control
interval
min 1 1 - 30 The time interval at which the set point is re-calculated,
based on changing external influences.
Table 21 Parameter list of the hybrid control module