Technical data

Table Of Contents
COMMISSIONING
6 720 803 687 (2012/11)34
6.2.6 CONNECTING THE PROGRAMMING UNIT TO THE HYBRID
CONTROL MODULE
Use only one FW200 programming unit per hybrid system. Connect this
to the hybrid control module.
Mount the FW200 programming unit separately on a wall, if the unit has
been previously fitted in the front of the boiler unit, it must be removed
and fitted externally as stated.
CONNECTIONS INSIDE THE HYBRID MANAGER
Fig. 44 Connections at the hybrid manager
[1] Connections for the ISM CANBUS cable
[2] Connections for the FW200 programming unit
[3] Connections for the heat source
Remove the front cover of the hybrid control module.
Undo fixing screws.
–Flip up and remove front cover.
Fig. 45 Removing the front cover of the hybrid control module
Route the cable through the cable guide behind the insulation.
Fig. 46 Cable guide inside the hybrid manager
Connect the two-core CANBUS cable of the FW200 programming unit
to terminals 16 and 17 to the hybrid control module and the
programming unit.
Recommended wire size: 0.75 mm
2
(≥0.5 mm
2
)
Replace cover when finished.
6.2.7 CONNECTING THE HEAT SOURCE TO THE HYBRID
MANAGER
Route the cable through the cable guide behind the insulation.
Connect the two-core CANBUS cable from the heat source to
terminals 18 and 19 at the hybrid control module and the heat source.
Press and hold the back button for approximate 5 seconds to reset the
hybrid control module ( Fig 51, page 44).
6.2.8 COMMUNICATION ERROR FROM EXTERNAL UNIT ON
INITIAL POWER ON OF EXTERNAL UNIT AND HYBRID
MANAGER
It may be necessary to adjust Dip switch SW8-3 on the External Unit
controller circuit board if a communication error from the External Unit
is present during power on of the External unit and the Hybrid Manager.
Because the Hybrid Manager and External Unit have separate power
supplies, it may not be possible for both units to be powered ON at the
same time.
The External Unit and Hybrid Manager are separately located and if only
one installer is available to switch on both units, the timing to switch ON
the External Unit and Hybrid Manager will be different.
6720803687-36.1Wo
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
0...10VM2 BUSBUSTSCTSRM1
14 15 16 17 18 19 20
BUSBUS
2
31
6 720 646 970-29.3ITL
Terminals Connections
14, 15 Additional ISM module unit
16, 17 FW200 programming unit
18, 19 Heat source
Table 11 Connections at the hybrid control module
For Connection's to the heat source always consult the
installation manual.
It may be necessary to adjust Dip switch SW8-3 on the
External Unit controller circuit board if a communication
error from the External Unit is present during power on
of the External unit and the Hybrid Manager.
1
2
3
6720646970-107.2Wo