Installation Guide
FPP-RNAC-8A-4C | Operation and Installation Guide | 
. 
Bosch Security Systems, Inc. | 8/09 | F01U025431-02  5
1.8  Expander Supervision 
A watchdog supervises the operation of the 
FPP-RNAC-8A-4C processor and attempts to restart 
it if it fails. If the processor does not restart, or the 
power fails entirely, the installer-supplied EOL device 
disconnects from the input to report the trouble 
condition. If power is available, the System Trouble 
LED lights if the system encounters an error. 
1.9  Auxiliary Power Supply 
The FPP-RNAC-8A-4C can be wired to supply 
unsupervised constant auxiliary power through its 
NAC outputs. Refer to Section 
3.7.2 Auxiliary Circuits 
on page 
16 for additional information. 
2.0  Installing the FPP-RNAC-8A-4C 
The FPP-RNAC-8A-4C board and the enclosure are shipped together. The board, however, needs to be 
mounted into the enclosure. Hardware for mounting the board in the enclosure is supplied in the hardware 
pack. 
Figure 1:  FPP-RNAC-8A-4C Remote NAC Power Supply Board 
T
R
O
U
B
L
E
T
R
O
U
B
L
E
AC
I
N
P
U
T
1
I
N
P
U
T
2
EOL
REF
O
U
T
P
U
T
4
O
U
T
P
U
T
3
O
U
T
P
U
T
1
O
U
T
P
U
T
2
OPTION BUS
R Y G B
- AUX POWER +- BATTERY +
REPLACE WITH 15A
BLADE TYPE FUSE
BOSCH 
4998149856
INPUT ACTIVE
AC OK
SYSTEM TROUBLE
GROUND FAULT
TROUBLE 4
TROUBLE 3
TROUBLE 2
TROUBLE 1
TROUBLE
RESET
FLASH
PROGRAMMING
PORT
GROUND FAULT
OPEN = DISABLE
CLOSE = ENABLE
1
2
3
4
8
9
10
11
12
13
14
5
6
7
15
16
1  AC Input Select Switch 120/240 VAC 
2  AC Power Input 120/240 VAC 
3  Option bus 
4  Ground fault switch 
5  Flash programming port 
6  TROUBLE RESET button 
7  AC trouble relay output 
8  Trouble relay output 
9  NAC inputs 
10  EOL reference resistor (1kΩ to 20kΩ) 
11 NAC outputs 
12  Auxiliary 24V filtered and regulated output 
power 
13  Replaceable 15A fuse 
14  Battery input 
15  Configuration DIP switches 
16  Status LEDs 