Installation Guide
FPP-RNAC-8A-4C | Operation and Installation Guide | 1.0  Overview
4  Bosch Security Systems, Inc. | 8/09 | F01U025431-02
1.0 Overview 
The FPP-RNAC-8A-4C is a Remote Notification 
Appliance Circuit (NAC) Power Supply designed to 
add four additional NACs (NFPA 72 Class B, Style Y 
or Class A, Style Z) to a Fire Alarm Control Panel 
(FACP). 
The FPP-RNAC-8A-4C is supervised by the control 
panel. It consists of the controller board, backup 
batteries, and enclosure. 
The FPP-RNAC-8A-4C is also compatible with any 
UL Listed control unit utilizing: 
•  reverse polarity supervised notification appliance 
circuit (NAC) outputs, and 
•  12 or 24 VDC regulated outputs. 
Each output can be configured individually as a NAC 
or constant 24 V auxiliary power supply. 
1.1  Module Control 
1.1.1  Option Bus Control 
The FPP-RNAC-8A-4C can connect to the Option 
Bus of the FPA-1000 or FPD-7024 Fire Alarm 
Control/Communicator. 
Refer to Section 
3.3 Option Bus Connections on 
page 
14 for information on wiring. 
1.1.2  Conventional NAC Input Control 
For conventional panels, the FPP-RNAC-8A-4C 
connects using the FACP’s NAC outputs that conform 
to NFPA 72 Class A or B. Please refer to the control 
panel’s NAC compatibility information. 
1.2  Output Bell Operation 
The FPP-RNAC-8A-4C can generate three pulsed 
bell patterns on command in addition to steady 
activation of the output: 
•  Pulsed: 60 PPM (0.5 sec On, 0.5 sec Off) 
•  NFPA Temporal: In compliance with ANSI 
standard S3.41: 0.5 sec On, 0.5 sec Off, 0.5 sec 
On, 0.5 sec Off, 0.5 sec On, 1.5 sec Off, and so 
on. 
•  California March: 120 ppm (0.25 sec on, 
0.25 sec off). 
You can also implement SYNC protocols: 
•  Wheelock SYNC Protocol 
•  Gentex SYNC Protocol 
•  System Sensor SYNC Protocol 
All outputs are synchronized if the 
conventional inputs are activating the 
FPP-RNAC-8A-4C. 
For option bus synchronization 
information, refer to the control panel 
documentation. 
1.3 Power Management 
The controlling section of the board has un-
interruptible power. If AC line voltage is lost, the 
power supply switches to battery backup. 
1.4  Low AC Line Detection 
Sensing circuitry detects a line input voltage below 
85 VAC, then switches from the primary AC Line 
voltage to battery backup. 
1.5  Ground Fault Monitoring 
The option bus and polarity reversal inputs are 
electrically isolated from the local power supply and 
indicating circuits. The FPP-RNAC-8A-4C supervises 
itself for grounded field connections and indicates a 
fault condition if one is found. This feature can be 
disabled by opening Switch S4. 
For UL864 installations, do not disable 
ground fault monitoring. 
1.6  Circuit Supervision 
Each NAC is supervised for short-circuit and open 
conditions using an end-of-line (EOL) resistor on the 
loop. Devices on these loops must have a blocking 
diode on their input so that the EOL supervision 
resistor can be read when the polarity of the output is 
reversed in the standby state. The devices activate 
when the polarity is switched back to normal in an 
alarm state. The EOL is programmable from 1 kΩ to 
20 kΩ. This allows existing systems to be retrofitted. 
1.7  Overvoltage Supervision 
The power supply output is monitored for overvoltage 
conditions. If an overvoltage condition exists (30 V or 
more on battery leads without the battery connected), 
the trouble relay and EOL relays open. In addition, 
the trouble LED lights. On the option bus, AC fail, 
ground fault, and NAC troubles are initiated. 










