Installation Guide
FPP-RNAC-8A-4C | Operation and Installation Guide | 6.0  Specifications
24  Bosch Security Systems, Inc. | 8/09 | F01U025431-02
Table 11: Specifications (continued) 
Trouble Relay Output 
Contact Type  Form C 
Contact Rating  1.5 A, 30 VDC resistive load 
AC Trouble Relay Output 
Contact Type  Form C 
Contact Rating  1.5 A, 30 VDC resistive load 
Power Output Circuit when Notification Appliance Circuit (NAC) is Configured as a Power Output Circuit 
Output Voltage  24 VDC Nominal 
Range for Compatibility  19.6 to 27.5 VDC 
Output Current  1.3 A maximum 
Ripple Voltage  250 mVpp 
Maximum current of 8 A is shared among all notification appliance circuits (NAC), power output circuits, and 
auxiliary power circuit. Power Limited, Special Application. 