Installation Guide
FPP-RNAC-8A-4C | Operation and Installation Guide | 4.0  DIP Switch and Option Bus Settings
20  Bosch Security Systems, Inc. | 8/09 | F01U025431-02
4.4  Option Bus Address 
To activate a new address, remove the 
AC and battery power from the 
FPP-RNAC-8A-4C. Wait 60 sec. Restore 
the power after it is removed. The new 
address becomes active after power is 
restored to the FPP-RNAC-8A-4C. 
The FPP-RNAC-8A-4C needs its own address 
(1 to 14) when using the option bus connection. Use 
Switch S2, Positions 3 through 6. 
Refer to 
Figure 13 on page 22 for the correct DIP 
switch positions. 
4.5  NAC Input Variable 
Instead of having Input 1 drive NAC Output 1 and 2 
and Input 2 drive NAC Output 3 and 4, Input 1 can be 
set to drive all four outputs. Set Switch S1 to the ON 
position to select this option. 
4.6  AC Fail Time Delay 
A trouble condition is registered to the control panel 
but is not indicated with an LED if the AC falls below 
85/105V for more than 5 sec. A programmable time 
delay allows the indication of AC failure to be delayed 
by 0, 1, 3, or 6 hr. The default value is 0 hr. 
Use Switch S2 positions 1 and 2 for these settings. 
UL864 requires that off-premises 
signaling of AC Trouble is delayed 
between 60 and 180 minutes. 
To comply with this requirement: 
•  Set the AC Fail Time Delay to 0, and 
•  Program the FACP to delay the off-
premises AC Trouble signal to a 
value between 60 min and 180 min. 