Installation Guide
FPP-RNAC-8A-4C | Operation and Installation Guide | 4.0  DIP Switch and Option Bus Settings
. 
Bosch Security Systems, Inc. | 8/09 | F01U025431-02  17
4.0  DIP Switch and Option 
Bus Settings 
Use DIP Switch S1 to set the following options: 
•  Output pattern or protocol 
•  NAC or power supply mode 
Use DIP Switch S2 to set: 
•  NAC input variable 
•  AC failure time delay 
•  Option bus address 
Refer to: 
• 
Figure 1 on page 5 for the location of the DIP 
switches on the FPP-RNAC-8A-4C board 
• 
Figure 12 on page 5 for the details of Switches S1 
and S2 
• 
Table 7on page 17 and Table 8 on page 18 for 
the DIP switch positions and settings. 
4.1 Switch S1 
Positions 0, 1, and 2 on Switch S1 control the bell 
output pattern or the synchronization (SYNC) 
protocol. 
Positions 3 through 6 on Switch S1 control the output 
mode. 
•  If the switch is OFF, the output is in NAC mode. 
•  If the switch is ON, the output is in power supply 
(POWER) mode. 
Each output can be configured individually to operate 
in the NAC or power supply mode. When the output is 
in the NAC mode, it follows either the option bus 
command or the DIP switch settings depending on 
the FPP-RNAC-8A-4C connection. 
In the power supply mode, the output is turned on all 
the time and is no longer supervised by an EOL. The 
commands from the option bus and pattern settings 
are ignored for any output configured in the power 
supply mode. 
Table 7: DIP Switch S1 Settings 
Bell Pattern and Protocol Output Options  Output Mode Options 
Position Name 
SYNC 2  SYNC 1  SYNC 0 
NAC 4/ 
POWER 4 
NAC 3/ 
POWER 3 
NAC 2/ 
POWER 2 
NAC 1/ 
POWER 1 
Position 
Number  0  1  2 
3 
4  5  6 
Notes 
Steady 
Follower
1
OFF OFF OFF 
OFF (NAC) 
ON (PWR) 
OFF (NAC) 
ON (PWR) 
OFF (NAC) 
ON (PWR) 
OFF (NAC) 
ON (PWR) 
Pulsed
1
 Pattern  OFF  OFF  ON 
OFF (NAC) 
ON (PWR) 
OFF (NAC) 
ON (PWR) 
OFF (NAC) 
ON (PWR) 
OFF (NAC) 
ON (PWR) 
California March 
Time
1
OFF ON OFF 
OFF (NAC) 
ON (PWR) 
OFF (NAC) 
ON (PWR) 
OFF (NAC) 
ON (PWR) 
OFF (NAC) 
ON (PWR) 
Temporal Code 
Three
1
OFF  ON  ON 
OFF (NAC) 
ON (PWR) 
OFF (NAC) 
ON (PWR) 
OFF (NAC) 
ON (PWR) 
OFF (NAC) 
ON (PWR) 
Wheelock
2 
SYNC Protocol 
ON OFF OFF 
OFF (NAC) 
ON (PWR) 
OFF (NAC) 
ON (PWR) 
OFF (NAC) 
ON (PWR) 
OFF (NAC) 
ON (PWR) 
Gentex
2
 SYNC 
Protocol 
ON  OFF  ON 
OFF (NAC) 
ON (PWR) 
OFF (NAC) 
ON (PWR) 
OFF (NAC) 
ON (PWR) 
OFF (NAC) 
ON (PWR) 
System Sensor
2 
SYNC Protocol 
ON ON OFF 
OFF (NAC) 
ON (PWR) 
OFF (NAC) 
ON (PWR) 
OFF (NAC) 
ON (PWR) 
OFF (NAC) 
ON (PWR) 
1  When operating in NAC mode (Switch S1, position 3, 4, 5, or 6-= OFF), the FPP-RNAC-8A-4C produces the protocol 
selected for the output. 
2  When operating in one of the SYNC protocols, NAC Input 1 controls strobes and Input 2 controls sounders. This 
protocol allows the sounders to silence while strobes continue to operate. When silenced, the output signal generates 
the silence pattern for that protocol. Switch S2, Position 1 is ignored.