Installation Guide
FPP-RNAC-8A-4C | Operation and Installation Guide | 
12  Bosch Security Systems, Inc. | 8/09 | F01U025431-02
You can use the format in 
Table 3 to calculate the required battery size to support the system. Use Table 4 and 
Table 5 on page 13 to estimate the required battery size. 
Table 3: Standby Time Calculation 
Device  Quantity  Standby 
Current for 
Each Device 
Total Standby 
Current for Each 
Device (Quantity x 
Standby Current for 
Each Device) 
Alarm Current 
for Each Device 
Total Alarm 
Current for Each 
Device (Quantity x 
Alarm Current for 
Each Device) 
FPP-RNAC-8A-4C 
Remote NAC Power 
Supply 
1  150 mA  150 mA  150 mA  150 mA 
    Grand Total 
Standby Current 
  Grand Total 
Alarm Current 
Table 4: Calculating the Required Battery Size 
Descriptions Calculations 
Grand Total Standby Current (in amps [A])  CS 
Total Hours of Standby Required (usually 24 or 60)  HS 
Total Standby Capacity (multiply CS x HS)  TS = CS x HS 
Grand Total Alarm Current (in amps)  CA 
Divide by 0.6  CAA = CA รท 0.6 
Total Hours of Alarm Time Required (usually 0.083 [5 min.] or 0.25 [15 min.])  HA 
Total Hours Capacity (multiply CAA x HA)  TA = CAA x HA 
Total Alarm Capacity Required (add TA + TS)  TC = TA + TS 
Required Capacity with 20% Derating (TC x 1.2)  C = TC x 1.2 