User guide

2. Change password
A list of all operators is displayed.
Refer to Scrolling through lists, page 27 for information on how to navigate through a list.
3. Select the list field you require.
4. Enter the password.
On the display, each digit of the password is indicated with an asterisk so that nobody
else can see the password.
5. Enter a new password and repeat the entry in the bottom field again.
6. Select OK to confirm the entry or Cancel to cancel the operation.
Performing a fire drill
During a drill, all signaling devices are activated.
!
Caution!
If a genuine alarm is reported during a fire drill, the fire drill is abandoned. The fire drill can
only be restarted when the alarm is ended.
To start a drill:
1. In the start menu, select Further functions
2. Drill
3. Confirm Start drill with OK
The drill is started.
To end the drill, select Stop drill.
During the fire drill, fire alarms, fault messages and supervisory alarms are displayed.
To switch between the fire drill display and the message display in question, select Return to
message screen or Return to drill screen on the status bar.
If an alarm or a fault/supervisory alarm is sounded during a fire drill, the panel controller
reacts as described in the table below:
Fire alarm Fault/ supervisory alarm
The drill signaling devices are
switched off.
Yes No
The drill is automatically
terminated.
Yes No
Display switches to Alarm indication Fault indication
Fire drill after event ends Must be restarted
manually
Continue
A new function cannot be selected until the fault/supervisory alarm and/or the fire drill have
been completed.
Alarm Counters
Show Lifetime Event Counters
During the lifetime of the panel, the following alarm messages are counted:
External alarm: all fire messages
Internal alarm: all alarm messages that the panel receives in day mode
Walktest alarm: all messages from detectors switched to walktest
To display the number of alarm messages which have been counted so far:
1. In the start menu, select Further functions
20.6
20.7
Panel Controller Further functions | en 91
Bosch Sicherheitssysteme GmbH User Guide 2013.07 | 3.0 | F.01U.258.929