Data Sheet
Certifications and approvals
Region Certification
USA UL UNIU: Boxes, Non-Coded (UL38)
CSFM see our website
FDNY-
CoA
#6173
Installation/configuration notes
Compatibility Information
The following table lists control panels compatible
with the FMM‑7045 and FMM-7045-D manual stations:
Control Panels
Active products:
FPD-7024
Legacy products:
D7024*
* with firmware revision 2.0 or greater and with a D7039 Multiplex
Expansion module
Addressing
Addresses are set using three rotary switches.
For programming information, refer to the D7024 FACP
Operation and Installation Guide or the FPD‑7024
Operation and Installation Guide and the FMM-7045,
FMM-7045-D Multiplex Addressable Manual Stations
Installation Instructions.
Mounting
The manual stations are for indoor use only.
Notice
If a pull station is needed for outdoor use or in an
unheated area, use an FMM‑100 Family Pull
Station rated for the environment and wired to a
multiplex module within the interior of the
building.
The FMM‑7045 manual stations flush or surface mount
on a standard four‑inch square back box with a
single‑gang mud ring so that the total depth of the box
is at least 2.25 in. (5.7 cm).
Notice
These manual stations do not fit an FMM‑100BB‑R
Back Box.
Wiring
The terminal block accepts wiring up to 12 AWG (ISO
4 mm
2
) in diameter.
For multiplex wiring information, refer to the D7039
Installation Instructions.
Parts included
Quant. Component
1 Manual station
1 FMM‑100GR Scored Acrylic Breakrod
1 D102 Key (1358)
1 Literature pack
Technical specifications
Environmental Considerations
Environment: Dry, indoor
Radio Frequency
Interference (RFI)
Immunity:
No alarm on critical frequencies in the
range from 26 MHz to 950 MHz at field
strengths less than 30 V/m.
Temperature
(Operating):
+32°F to +120°F (0°C to +49°C)
Mechanical Properties
Dimensions (H x W x D): 4.75 in. x 3.75 in. x 3.25 in.
(12 cm x 9.5 cm x 8.2 cm)
Material: Die cast zinc alloy and steel
Power Requirements
Current Draw (Mux Bus
Average):
Alarm: 0.55 mA
Standby: 0.55 mA
Voltage (Operating): 12 VDC nominal (provided by the MUX
bus)
Ordering information
FMM‑7045 Single‑Action Manual Station
The single‑action manual station is UL listed and meets
Americans with Disabilities Act (ADA) requirements. Its
address on the polling circuit is easily set with rotary
switches. The pull handle locks in the activated
position and is reset by opening the unit with a key
and then relocking it.
Order number FMM-7045
FMM‑7045‑D Double‑Action Manual Station
The double‑action manual station is UL listed and
meets Americans with Disabilities Act (ADA)
requirements. Its address on the polling circuit is
easily set with rotary switches. The pull handle locks in
the activated position and is reset by opening the unit
with a key and then relocking it.
Order number FMM-7045-D
Accessories
D102 Replacement Key
Replacement key (#1358) for LOCK‑1358 and the
D101 lock.
Order number D102
2 | FMM‑7045 Multiplex Addressable Manual Stations