Safety Notes
Functional description
The FLM-420-RLV1 Relay Interface Module Low Voltage has a change-over contact relay to provide a potential free
output contact.
The FLM-420-RLV1-D is installed on a DIN rail in accordance with EN 60715 with enclosed adapter (see Figure 1,
Page 4; Removal, see Figure 2, Page 5).
Address setting
Fit a rotary switch in the required position using a pan head slotted screwdriver (see Figure 4, Page 6).
Connection
Technical Specifications
NOTICE!
Installation must only be performed by authorized and specialized personnel!
The connected device must have a minimum activation time of 20 ms.
CAUTION!
Electrostatic discharge (ESD)! Electronic components could become damaged.
Ground yourself using a wrist strap or take other suitable actions.
Address (A) Operating mode
0 0 0 Loop/stub in LSN improved version mode with automatic addressing
0 0 1 - 2 5 4 Loop/stub/T-taps in LSN improved version mode with manual addressing
CL 0 0 Loop/stub in LSN classic mode (address range: max. 127)
2 5 5 - 2 9 9 Non-permitted address range (error message on fire panel)!
Terminals Function
LSN: b1+ | a- | b2+ LSN incoming/LSN outgoing
REL1: NC | COM | NO Change-over relay (NC contact/COM/NO contact)
Figure 5, Page 6 shows the relay connected as
- NC contact: continuous line
- NO contact: dotted line.
Relay 1 low voltage relay (NC/COM/NO)
LSN input voltage 15 to 33 V DC
Max. current consumption from LSN 1.75 mA
Contact load (resistive load)
- Max. switched current and voltage 5 A / 30 V DC; 0.5 A / 42.4 V AC
- Min. switched current and voltage 0.1 mA / 100 mV DC; 0.1 mA / 100 mV AC
- Max. AC frequency 100 Hz
Minimum activation time of the connected device > 20 ms
Permissible wire diameter
0.6 to 3.3 mm
2
Permissible operating temperature -20 °C to +55 °C
Permissible storage temperature -25 °C to +80 °C
Permissible rel. humidity <96 %, non-condensing
Protection class as per IEC 60529 IP 30
Classes of equipment as per IEC 60950 Class III equipment
Housing material and color PPO (Noryl), gray white (similar to RAL 9002)
Dimensions (with adapter ) Approx. 110 mm x 110 mm x 48 mm (W x H x D)