Technical Specifications
Operating/display elements 2 LEDs (1 x red, 1 x green)
Function selection FAN or RLHV function via rotary
switch
Input voltage 15 V DC to 33 V DC
Max. current consumption 17.15 mA
Max. contact load - 10 A at 120 V AC / 230 V AC /
24 V DC
- 6 A at 30 V DC
Max. bounce period of NC contact 9 ms
Fuses (F1/F2) 10 A / 250 V; type TH, slow, high
breaking
Feedback current max. 1 mA (EOL resistor R = 3.9 kΩ)
Feedback voltage max. 30 V DC
Permitted wire diameter
0.6 - 3.3 mm
2
Permitted operating temperature /
storage temperature
-20 °C to +50 °C / -25 °C to +80 °C
Permitted relative humidity <96 %, non condensing
Protection class as per IEC 60529 - FLM-420-RHV-D: IP 30
- FLM-420-RHV-S: IP 54
Classes of equipment as per
IEC 60950
Class II equipment
Material and color interface module
housing
PPO(Noryl), off-white (similar to
RAL 9002)
Material and color surface-mount
housing
ABS/PC-Blend, signal white
(RAL 9003)
Dimensions
- FLM-420-RHV-D (with DIN rail
adapter):
approx. 110 x 110 x 48 mm
- FLM-420-RHV-S: approx. 126 x 126 x 71 mm