Manual

10 en FLM-320-EOL4W-S
F.01U.121.918 | 5.0 | 2011.05 Bosch Sicherheitssysteme
Notes
Functions
The FLM-320-EOL4W-S is used to terminate conventional stubs. It can detect faults on the
conventional line and auxiliary voltage in accordance with EN 54-13, and uses the line to
report an error on the fire panel's operating panel.
Connection
Connect the EOL module as the last element in a conventional line. Set the resistance (R), the
voltage (V), and the power (P) for the line via the DIP switches, using the FSP-5000-RPS
programming software to calculate the values and the associated DIP settings.
Technical data
- Installation must only be performed by authorized and specialized personnel!
- An EOL module must be connected at the end of every conventional line.
- Country-specific standards and guidelines must be observed during installation.
- You are required to use the FSP-5000-RPS programming software for the FPA-5000 fire
panel to calculate which programming is required via the DIP switches.
Description Function
CONV b+ Conventional line, incoming
CONV a-
POWER +U Power supply
POWER 0V
Shield Cable shielding
POWER CONV
Shield +U 0V b+ a-
R
V
P
AUX input voltage 8 VDC to 30 VDC
Conventional input voltage 9 VDC to 30 VDC
AUX current consumption < 5.5 mA
Conventional current consumption < 2.0 mA
Housing material ABS + PC blend
Housing color Signal white, RAL 9003
Dimensions (H x W x D) Approx. 126 x 126 x 71 mm
Weight 342 g
Permitted operating temperature -20 °C to 55 °C
Permitted storage temperature -25 °C to 85 °C
Permitted relative humidity <96%, non-condensing
Protection class compliant with IEC 60529 IP 54