Technical data
PI - 34.85
Product Information Linear Smoke Detector Fireray 50/100RV
601-F.01U.002.705
A1.en / 29.12.2004
ST-FIR/ PRM1/ zab
Seite 19 von 22
10. Technical Data
Operating voltage 10 V DC . . . 30 V DC
Current consumption:
in standby mode
< 4 mA @ 24 V
-
i
n
s
t
an
db
y
mo
d
e
- in alarm/malfunction
<
4
m
A @ 24 V
< 15 mA
Reset control by power disruption > 5 s
Alarm relay Open contact, potential-
free
(2 A @ 30 V DC)
Fault relay Break contact element,
potential-free
(2 A @ 30 V DC)
Permissible distance between the detector and the
prism reflector:
- Fireray 50R
- Fireray 100R
5 m to 50 m
50 m to 100m
Optical wavelength 880nm
Adjustable alarm threshold values 2.50 dB (25%)
3.74 dB (35%)
6.02 dB (55%)
Axial deviation tolerance
(at 35% sensitivity)
Detector $0.8
Prism reflector $5.0
Operating temperature -30C . . . +55C
Protection type IP 50
Dimensions (W x H x D) 126 x 210 x 120 mm
Weight 670 g
Housing:
- Color
- Material
light gray/black
ABS, non-flammable
VdS ID number G 203 070