24 en FCS-320-TP1 | FCS-320-TP2 | FCS-320-TT1 | FCS-320-TT2
F.01U.130.927 | 2.0 | 2010.12 Bosch Sicherheitssysteme GmbH
Installation
FCS-320-TP1 and FCS-320-TP2 System Overview
See Figure 1, Page 4
FCS-320-TT1 and FCS-320-TT2 System Overview
See Figure 2, Page 4
Jumper Assignment
See Figure 4, Page 5
CAUTION!
Installation must only be performed by authorized and specialized personnel!Switch off the
unit before carrying out the following work.Do not connect or disconnect the detector module
while switched on!
1Operating LED
2 Alarm LED for detector module 1
3 Alarm LED for detector module 2 (for FCS-320-TP2 only)
4 Collective fault LED
5 Pre-punched cable entries for connection to the fire panel and power supply
(input/output)
6 Pipe system 1 connection
7 Pipe system 2 connection (required for FCS-320-TP2 only)
8 Connection for air return pipe
1 Operating LED
2 Collective fault LED
3 Info alarm LED for detector module 1
4 Pre-alarm LED for detector module 1
5 Main alarm LED for detector module 1
6 Smoke level display in ten levels, detector module 1
7 Info alarm LED for detector module 2 (for FCS-320-TT2 only)
8 Pre-alarm LED for detector module 2 (for FCS-320-TT2 only)
9 Main alarm LED for detector module 2 (for FCS-320-TT2 only)
10 Smoke level display in ten levels, detector module 2 (for FCS-320-TT2 only)
11 Pre-punched cable entries for connection to the fire panel and power supply (input/
output)
12 Pipe system 1 connection
13 Pipe system 2 connection (required for FCS-320-TT2 only)
14 Connection for air return pipe
Jumper JU1: fan voltage Pin 1+2
6.9 V Bypassed
9V Open
Jumper JU2: collective fault contact for detector module 1 Pin 1+2 Pin 2+3
NC contact Bypassed Open
NO contact Open Bypassed
Jumper JU3: collective fault contact for detector module 2 Pin 1+2 Pin 2+3
NC contact Bypassed Open
NO contact Open Bypassed
Jumper JU4: number of detector modules Pin 1+2
1 detector module Bypassed
2 detector modules Open