Datasheet

FCP‑500 Conventional Automatic Fire Detectors | 5
FCP-500 Conventional Automatic Fire Detectors
FCP-O 500 FCP-O 500-P FCP-OC 500 FCP-OC 500-P
Detector type
optical optical optical/chemical optical/chemical
Operating voltage
8.5 V DC . . . 33 V DC 8.5 V DC . . . 33 V DC 8.5 V DC . . . 33 V DC 8.5 V DC . . . 33 V DC
Current consumption
- Standby current
FCA-500-EU: 3 mA
FCA-500-E-EU: 24 mA
FCA-500-EU: 3 mA
FCA-500-E-EU: 24 mA
FCA-500-EU: 3 mA
FCA-500-E-EU: 24 mA
FCA-500-EU: 3 mA
FCA-500-E-EU: 24 mA
- Alarm current
47 mA 47 mA 47 mA 47 mA
- Fault current
FCA-500-EU: 52 mA
FCA-500-E-EU: 58 mA
FCA-500-EU: 52 mA
FCA-500-E-EU: 58 mA
FCA-500-EU: 52 mA
FCA-500-E-EU: 58 mA
FCA-500-EU: 52 mA
FCA-500-E-EU: 58 mA
Protection category
IP 53 IP 53 IP 33 IP 33
Permissible operating
temperature
-20 °C . . . +65 °C -20 °C . . . +65 °C -10 °C . . . +50 °C -10 °C . . . +50 °C
Monitoring area
max. 120 m² max. 120 m² max. 120 m² max. 120 m²
Maximum installation
height
16 m 16 m 16 m 16 m
Color
white transparent with color
inserts
white transparent with color
inserts
www.boschsecurity.com