Datasheet

4 | FCP‑500 Conventional Automatic Fire Detectors
Environmental conditions
Protection class as per
EN 60529
FCP‑O 500 (‑P) IP 53
FCP‑OC 500 (‑P) IP 33
Permissible operating tem-
perature
FCP‑O 500 (‑P) -20 °C bis +65 °C
FCP‑OC 500 (‑P) -10 °C bis +50 °C
Permissible relative humidity 95% (non-condensing)
Permissible air speed 20 m/s
Planning
Monitoring area
Max. 120 m
2
(Heed local guidelines!)
Maximum installation height Max. 16 m
(Heed local guidelines!)
Minimum installation height Out of arm's reach
Minimum installation height recommend-
ed by BOSCH: 2.70 m
In the case of flush ceiling
mounting with ceiling mount
back box
Thickness of the false ceiling Max. 32 mm
Required bored hole Ø 130 mm (-1 mm bis +5 mm)
Installation depth 110 mm
Note: Above the false ceiling, a free height
of at least 110 mm is required.
Minimum distance to lamps 0.5 m
Special features
Detection principle
FCP‑O 500 (‑P)
Scattered light measurement
FCP‑OC 500 (‑P)
Combination of scattered light measurement
and combustion gas measurement
Features
All FCP‑500 detec-
tors
Contamination detection
Drift compensation (optical section)
In addition, for
FCP‑OC 500(-P)
Drift compensation in the gas sensor section
Response sensitivity
FCP‑O 500 (‑P)
< 0.18 dB/m ( EN 54‑7)
FCP‑OC 500 (‑P)
Optical section: < 0.36 dB/m (EN 54‑7)
Gas sensor section: in ppm range
Ordering Information
FCP‑O 500 Optical Smoke Detector, White
ultra-flat design, conventional technology
FCP-O 500
FCP‑O 500‑P Optical Smoke Detector,
Transparent with Color Inserts
ultra-flat design, conventional technology
FCP-O 500-P
FCP‑OC 500 Multisensor Detector Optical/
Chemical, White
ultra-flat design, conventional technology
FCP-OC 500
FCP‑OC 500‑P Multisensor Detector
Optical/Chemical, Transparent with Color
Inserts
ultra-flat design, conventional technology
FCP-OC 500-P
Accessories
FAA‑500‑TR-W Trim Ring, White
for 500 and 520 Series Fire Detectors
FAA-500-TR-W
FAA‑500‑TR‑P Trim Ring, Transparent with
Color Inserts
for 500 and 520 Series Fire Detectors
FAA-500-TR-P
FCA‑500‑EU Conventional Base
for the FCP‑-500 Series detectors
FCA-500-EU
FCA‑500‑E‑EU Conventional Base EOL
for the FCP‑500 Series detectors, with inte-
grated EOL resistor
FCA-500-E-EU
FAA‑500‑BB Ceiling Mount Back Box
for ceiling flush installation in false ceilings
when mounting 500 and 520 Series Bases
and Fire Detectors
FAA-500-BB
FAA‑500‑CB Built-in Housing for Concrete
Ceilings
for installing 500 and 520 Series Fire Detec-
tors in concrete ceilings. In addition, you
need to order a FAA‑500‑BB Ceiling Mount
Back Box, which contains the base and the
detector.
FAA-500-CB
FAA‑500‑SB Surface Mount Back Box
for special applications where it is not possi-
ble to flush-mount the 500 and 520 Series
Fire Detectors in a ceiling
FAA-500-SB
FAA‑500‑SB-H Surface Mount Back Box
with Damp Room Seal
for special applications where it is not possi-
ble to flush-mount the 500 and 520 Series
Fire Detectors in a ceiling
FAA-500-SB-H
FAA‑500‑SPRING for Concrete/Wooden
Ceilings
(DU = 10 units)
FAA-500-SPRING