Data Sheet
Certifications and approvals
3M (Macurco) holds these Listings and Approvals.
Meets NFPA 720‑2009 standards for CO sensor functionality and
sensitivity testing.
Region Certification
USA UL FTAM: Gas and Vapor Detectors and
Sensors (UL2075)
CSFM see our website
Installation/configuration notes
Compatibility Information
The carbon monoxide detector is compatible with all
UL Listed control panels that have 12 VDC to 24 VDC
power and alarm initiating circuits. The detector can
also be used with a UL Listed Class 2 power supply.
Mounting Considerations
There are two usual sources of CO - defective heat
sources (furnaces or wood burning stoves) and
automobiles running in adjoining garages. The detector
can detect CO from these sources, as well as any
other sources of CO. For best operation, mount a
detector in the hallway near each bedroom or office
area. In addition, another detector can be mounted
just inside the door from the adjoining garage.
Consider placing another detector in a bedroom or
office that is adjacent to a furnace room. The detector
may be installed on either a ceiling or a wall. If
installed on a peaked, gabled, or sloped ceiling, it
should be located about 3 ft (1 m) from the highest
point. The unit can be placed vertically or horizontally
on a wall, so the information on the front of the
detector can be read in a normal manner (not upside
down). Do not mount the detector in a corner. Use the
same spacing as for smoke detectors – 30 ft (9 m)
centers, 900 ft
2
(84 m
2
) per detector.
Wiring Considerations
Use the indicated wire size for the detector loop:
Length of Wire Run Recommended Wire Size
200 ft (61 m) or less 22 AWG (0.8 mm)
Up to 575 ft (175 m) 20 AWG (1.0 mm)
Up to 686 ft (209 m) 18 AWG (1.2 mm)
Up to 1300 ft (396 m) 16 AWG (1.5 mm)
Up to 2100 ft (640 m) 14 AWG (1.8 mm)
Up to 3200 ft (975 m) 12 AWG (2.3 mm)
Terminate each loop with an end-of-line resistor as
specified by the control panel's installation
instructions.
Parts included
Quant. Component
1 Carbon monoxide detector
1 Literature pack
Technical specifications
Electrical
Current
Alarm: 35 mA at 9 VDC to 32 VDC
Normal: 15 mA at 9 VDC to 32 VDC
Voltage
VDC input: 9 VDC to 32 VDC
Environmental
Temperature
(operating):
+40°F to +100°F (+4.4°C to +37.8°C)
Mechanical
Color: White
Dimensions (H x W x
D):
5.125 in. x 3.125 in. x 1. 5 in.
(13 cm x 8 cm x 3.8 cm)
Weight (shipping): 1 lb (0.45 kg)
Outputs
Alarm
Relay Configuration: one NO or NC SPST (no polarity)
Relay Rating: 100 mA, 40 VDC
Sound Level: 85 dBA at 10 ft (3 m)
Trouble
Relay Configuration: one NC SPST (no polarity)
Relay Rating: 100 mA, 40 VDC
Trademarks
All hardware and software product names used in this
document are likely to be registered trademarks and
must be treated accordingly.
Ordering information
FCC‑380 Carbon Monoxide Detector (Macurco CM‑E1)
Carbon monoxide detector
Order number FCC-380
2 | FCC‑380 Carbon Monoxide Detector (Macurco CM‑E1)