Automatic Fire Detectors LSN improved
version
Maintenance and Service | en 31
Bosch Sicherheitssysteme GmbH Product Information F.01U.003.449 | 7.2 | 2010.05
8.1 Notes for the Service
8.1.1 Display of Operating Data in WinPara
Module Address
Module where the detector or detector line is installed.
Address
Detector installation address, e.g. 10-03: The detector is in zone 10 and is the detector
number 3.
Brief Info
Additional information entered during programming. e.g. "FAP-O 420 on MSS400" means that
the FAP-O 420 is installed together with an MSS 400 Detector Base Sounder. You can also
enter the position of the detector here.
Type
display of the set detector type.
Serial number
The first digit of the 8-digit serial number represents the year of manufacture, i.e. a detector
with the serial number 3931859 was manufactured in 2003.
Current analog values
NOTICE!
The DO detectors are not supported by the WinPara programming software.
NOTICE!
With the exception of the special KKW detector types, you can use the WinPara programming
software (V 4.53 or higher) to display the serial number, contamination level, operating hours
and current analog values for all configured detectors.
Optical system value (display of the current contamination value):
0 . . . 170 Initial set-up value for a new detector
0 . . . 350 Normal working range
350 . . . 450 Slight contamination: Exchange detector soon
450 . . . 510 Heavy contamination: Exchange detector immediately
From 511 O fault: optical sensor is deactivated!