Automatic Fire Detectors LSN improved
version
Accessories | en 25
Bosch Sicherheitssysteme GmbH Product Information F.01U.003.449 | 7.2 | 2010.05
Connection depending on the line technology
Line technology Fire panel Terminals
Conventional BZ 1060 1 + 2
Conventional FPA-5000, UEZ 1000, UGM 2020, FP 102/104/106 1 + 3
LSN FPA-5000, FPA-1200, BZ 500 LSN, UEZ 1000,
UEZ 2000 LSN, UGM 2020
1 + 4
Terminal Connection
1Ground
2 Entry point flashing (LED flashes)
3 Entry point static (LED flashes)
4 Entry point static (LED flashes)
A resistor is necessary to connect to terminal 4; otherwise, the LED
may be damaged.
All current Bosch detectors are equipped with an internal resistor to
restrict current consumption.
1234
CAUTION!
If the current consumption for the connected detector exceeds 20 mA, it can lead to the
malfunction of or damage to the MPA.
You should restrict the maximum detector current consumption to 20 mA to avoid damaging
the MPA.
NOTICE!
The cable length between the detector and the MPA must not exceed 3 m when connected by
an unshielded cable.
MPA technical specifications
Operating voltage 9 V DC to 30 V DC
Maximum current consumption
– Terminal 2
– Terminal 3
– Terminal 4
– approx. 2 mA
– limited to approximately 13 mA
– limit to maximum 20 mA
Display medium 1 LED
Permissible wire gauge 0.6 mm. . . 0.8 mm
Dimensions 79 x 79 x 31 mm
Weight Approx. 65 g
VdS approval number G 294 052