Automatic Fire Detectors LSN improved version FAP-DO420/FAP-420/FAH-420 en Product Information
Automatic Fire Detectors LSN improved version Table of Contents | en 3 Table of Contents 1 Product Description 5 2 System Overview 6 2.1 Detector Configuration 6 2.2 Functional Description of the Sensor Technology 6 2.2.1 Optical Sensor (Smoke Detector) 6 2.2.2 Thermal Sensor (Heat Detector) 6 2.2.3 Chemical Sensor (Gas Sensor) 6 2.3 System Description 7 2.4 Flash Frequency and Error Detection 7 2.5 Features 7 3 Planning 9 3.
Automatic Fire Detectors LSN improved version en | Table of Contents 7 Order Information 28 7.1 Detector Variants 28 7.2 Detector Bases 28 7.3 Detector Accessories 28 7.4 Installation Accessories 29 7.5 Detector Base Sounders 29 7.6 Service accessories 29 8 Maintenance and Service 30 8.1 Notes for the Service 31 8.1.1 Display of Operating Data in WinPara 31 8.2 Detector Type Encoding 33 8.3 Test Instructions for LSN improved version Fire Detectors 33 8.3.
Automatic Fire Detectors LSN improved version 1 Product Description | en 5 Product Description NOTICE! This product information describes the entire product range for the FAP-420/FAH-420 Automatic Fire Detectors LSN improved version series. Wherever the term DO detector is used in this document, this refers to the following detectors: FAP-DO420, FAP-DOT420, FAP-DOTC420.
Automatic Fire Detectors LSN improved version en | System Overview 2 System Overview 2.1 Detector Configuration 1 Smoke measurement chamber with 3 4 optical sensor 2 Thermal sensor 3 Chemical sensor (covered on the cross- 2 section) 1 4 Individual display 5 PC board with evaluation electronics 6 MS 400 Detector Base 6 5 Figure 2.1 Detector Configuration 2.2 Functional Description of the Sensor Technology 2.2.
Automatic Fire Detectors LSN improved version 2.3 System Overview | en 7 System Description Up to three detection principles are integrated in FAP-420/FAH-420 series detectors: – Optical (for smoke): O – Dual-optical (for smoke): DO – Thermal (for heat): T – Chemical (for gas): C The individual sensors are programmed via the LSN network manually or using a timer. All sensor signals are analyzed continually by the internal signal analysis electronics (ISP) and are linked with each other.
Automatic Fire Detectors LSN improved version en | System Overview – You can only use DO detectors with the MPC-xxxx-B Panel Controller or the FPA-1200. The MPC-xxxx-A Panel Controller cannot be used. – In classic mode, can be connected to the BZ 500 LSN, UEZ 2000 LSN and UGM 2020 LSN fire panels and to other panels or their receiver modules with identical connection properties but with the existing LSN system limits. (Not DO detectors.
Automatic Fire Detectors LSN improved version 3 Planning | en 9 Planning NOTICE! FAP-420/FAH-420 Automatic Fire Detectors are not designed for exterior use. 3.1 Basic Installation/Configuration Notes – Multi-sensor fire detectors must be planned in line with the guidelines for optical detectors until a guideline for their planning is developed in collaboration with the VdS (see also DIN VDE 0833 Part 2 and VDS 2095): – – Maximum monitoring area 120 m2. – Maximum installation height 16 m.
4 Automatic Fire Detectors LSN improved version en | Programming Programming Programming occurs via a PC or laptop connected to the fire panel – With FSP-5000-RPS (Remote Programming System) for panels with LSN improved version line technology – With WinPara for panels with conventional LSN line technology (not DO-Melder). 420 series detectors are programmed by entering the area of operation.
Automatic Fire Detectors LSN improved version 4.
4.
Automatic Fire Detectors LSN improved version Programming | en Installation locations 13 Selectable sensitivity EDP room High High storage warehouse without vehicle traffic with combustion High engine Office (day mode) 4.
Automatic Fire Detectors LSN improved version en | Connection 5 Connection 5.1 Overview of Detector Bases Detectors in the FAP-420/FAH-420 series are operated in one of the detector bases listed below. The detector bases are suitable for surface and flush mounting, and provide separate fixing points for ceiling and flush mount back boxes. They also fit all common bore patterns. The bases are made from white ABS plastic (color similar to RAL 9010) and have a matte surface finish.
Automatic Fire Detectors LSN improved version 5.2 Connection | en 15 Installing the Base The detector bases are screwed to the even, dry surface using two screws approx. 55 mm apart. To feed cables through for surface mounting, punch out the prepared entry points (X) on the housing. For flush-mounted cable insertion, feed the cable through the opening in the middle of the base.
Automatic Fire Detectors LSN improved version en | Connection 5.3 Connection NOTICE! Keep shield wire as short as possible and insulate. 5.3.1 Connecting the MS 400/MSF 400 4 3 1 1 2 5 max.
Automatic Fire Detectors LSN improved version 5.3.2 Connection | en 17 Connecting the FAA-MSR 420 Maximum contact load (resistive load) of the change-over contact relay: – 62.5 VA: 0.5 A at 125 V AC – 30 W: 1 A at 30 V DC NC C NO 1 1 2 3 4 5 c max.
5.4 Automatic Fire Detectors LSN improved version en | Connection Detector Base Sounders Detector base sounders are used if acoustic alarm signaling is required directly at the fire source. Detector base sounders are available in four variants. – MSS 300 Detector Base Sounder White, for conventional line technology, activation via the C point of the detector in use. – MSS 300 WS-EC Detector Base Sounder White, for conventional line technology, with external activation (via an interface module).
Automatic Fire Detectors LSN improved version 5.5 Connection | en 19 Installation of the Detector Module NOTICE! The packaging for the multisensor detector with C sensor consists of tear-proof PE-ALU laminated film and must be cut open carefully. After installation and connection of the base, the detector head is set into the base and turned to the right as far as it will go. Detector bases are delivered with inactive locks. The detector module can be locked in the base (removal protection).
5.7 Automatic Fire Detectors LSN improved version en | Connection Addressing There are three rotary switches on the bottom of the detector; these are used to select automatic or manual address allocation with or without auto-detection. The following settings are possible: Rotary switch setting Address 000 Operating mode Loop/stub with LSN improved version mode and automatic address allocation (T-tapping not possible) = delivery status 001 Loop/stub/T-tapping with LSN improved mode and ...
Automatic Fire Detectors LSN improved version Accessories | en 6 Accessories 6.1 Support Plate for Detector Identification 21 The support plates are made from 1.8 mm thick ABS plastic and are clamped between the detector base and the ceiling. TP4 400 Support Plate The TP4 400 Support Plate is intended for an installation height up to 4 m and is designed for labels up to a size of approx. 65 x 34 mm.
Automatic Fire Detectors LSN improved version en | Accessories 6.4 MK 400 Detector Console The MK 400 Detector Console is used to install detectors above door frames or similar in compliance with DIBt. The console is supplied with a pre-mounted MS 400 Detector Base (the detector shown is not included in the scope of delivery). 6.
Automatic Fire Detectors LSN improved version Accessories | en 23 Installation 1. Before assembly, remove the cap from the base plate: To unlock the snap-fit hooks (see image, item C) with a flat object (e.g. screwdriver), press in and lift the cap carefully. 35 mm 80 mm 80 mm A B D C b a 2. Fit the FAA-420-RI directly to the ceiling or wall. To do this, secure the base plate to a level, dry surface with two (item E) or four (item F) screws. 57 mm 57 mm E __++ F G 3.
Automatic Fire Detectors LSN improved version en | Accessories Technical data 6.6.2 Operating voltage 5–30 V DC Weight 45 g Display medium 2 LEDs Permissible wire gauge 0.6–2 mm Maximum current consumption 20 mA MPA External Detector Alarm Display Installation note – Fitted directly to the wall or ceiling. – To feed cables through for surface mounting, punch out the prepared entry points (see Figure 6.1, item X) on the housing.
Automatic Fire Detectors LSN improved version Accessories | en 25 Connection depending on the line technology Line technology Fire panel Terminals Conventional BZ 1060 1+2 Conventional FPA-5000, UEZ 1000, UGM 2020, FP 102/104/106 1+3 LSN FPA-5000, FPA-1200, BZ 500 LSN, UEZ 1000, 1+4 UEZ 2000 LSN, UGM 2020 Terminal Connection 1 Ground 2 Entry point flashing (LED flashes) 3 Entry point static (LED flashes) 4 Entry point static (LED flashes) A resistor is necessary to connect to termin
6.7 Automatic Fire Detectors LSN improved version en | Accessories Service and Detector Test Accessories SOLO200 Detector Removal Tool The pivoting grips and three different diameters make the SOLO200 Detector Removal Tool suitable for removing and replacing most fire detectors. The plastic caps enable the fire detector to be securely gripped and protect the detector surface against damage.
Automatic Fire Detectors LSN improved version Accessories | en 27 Solo CO testing gas Spray can with CO testing gas for multisensor detectors with C sensor. Contents: approx. 4 l compressed gas DU = 12 pieces SOLO461 Heat Detector Tester The SOLO461 Heat Detector Tester is battery-operated and conducts hot air to the heat detector sensor.
Automatic Fire Detectors LSN improved version en | Order Information 7 Order Information 7.1 Detector Variants Type number Designation Product ID FAP-DOTC420 Dual-optical, thermal, chemical multisensor detector F.01U.116.034 FAP-OTC 420 Optical, thermal, chemical multisensor detector F.01U.508.816 FAP-DOT420 Dual-optical, thermal multisensor detector F.01U.116.033 FAP-OT 420 Multisensor Detector Optical/Thermal F.01U.508.815 FAP-DO420 Dual-optical smoke detector F.01U.116.
Automatic Fire Detectors LSN improved version 7.4 Order Information | en 29 Installation Accessories Type number Designation Product ID MK 400 Detector Console, for DIBt-compliant detector 4.998.097.924 installation above doors or similar, incl. detector base FMX-DET-MB Mounting bracket, with installation material for false 2.799.271.257 floors, no detector base 7.5 Detector Base Sounders Type number Designation Product ID MSS 300 Detector Base Sounder White, conventional line 4.998.025.
Automatic Fire Detectors LSN improved version en | Maintenance and Service 8 Maintenance and Service In Germany, maintenance work and inspection work on security systems are governed by the regulations of DIN VDE 0833; these regulations stipulate reference to the manufacturer’s instructions for maintenance intervals. – Maintenance and inspection work should be carried out regularly and by trained personnel. – BOSCH ST recommends carrying out a functional and visual inspection at least once a year.
Automatic Fire Detectors LSN improved version 8.1 Maintenance and Service | en 31 Notes for the Service NOTICE! The DO detectors are not supported by the WinPara programming software. NOTICE! With the exception of the special KKW detector types, you can use the WinPara programming software (V 4.53 or higher) to display the serial number, contamination level, operating hours and current analog values for all configured detectors. 8.1.
Automatic Fire Detectors LSN improved version en | Maintenance and Service Temperature value [°C] (display of the value currently being measured by the thermal sensor): FAH-T 420 -20 °C. . . +65 °C FAP-OT 420 -20 °C. . . +50 °C FAP-OT 420 -10 °C to +50 °C CO value: Display of the value currently being measured by the CO sensor The CO value specifies the currently-measured CO concentration.
Automatic Fire Detectors LSN improved version 8.2 Maintenance and Service | en 33 Detector Type Encoding With the exception of the FAP-O 420 and FAP-O 420-KKW, all detectors are fitted with a colored ring around the central individual display to identify the detector type. This facilitates inspection by service personnel. 8.
Automatic Fire Detectors LSN improved version en | Maintenance and Service NOTICE! The test head must remain over the detector until the detector has been triggered. The time taken to distribute the test aerosol in the test head and therefore the trigger time of the sensor can be up to 20 seconds. – The thermal sensor of the FAP-DOTC420 / FAP-DOT420 / FAP-OTC 420 / FAP-OT 420 is tested with the test device for heat detectors.
Automatic Fire Detectors LSN improved version 9 Technical Data | en 35 Technical Data DO detectors Detector Type FAP-DOTC420 Detection principle FAP-DOT420 FAP-DO420 Scattered-light Combination of: – Scattered-light measurement – Measurement of absolute measurement temperature and temperature increase – Combustion - - gas measurement Special features – Two optical sensors – Contamination detection – Drift compensation in the optical sensor – Operation switching/sensor - deactivat
Automatic Fire Detectors LSN improved version en | Technical Data Multisensor detector Detector type FAP-OTC 420 Detection principle FAP-OT 420 Combination of: Combination of: – – – – Scattered-light Scattered-light measurement measurement Measurement of absolute – Measurement of absolute temperature and temperature and temperature increase temperature increase Combustion gas measurement Special features – Contamination detection – Contamination detection – Drift compensation i
Automatic Fire Detectors LSN improved version Technical Data | en 37 Smoke and heat detectors Detector type FAP-O 420 / FAP-O 420 KKW Detection principle Scattered-light measurement FAH-T 420 / FAH-T 420 KKW Measurement of absolute temperature and temperature increase Special features – FAH-T 420 KKW: – Contamination detection – Drift compensation in the For use in areas with optical sensor elevated radioactivity – FAP-O 420 KKW: For use in areas with elevated radioactivity Operating vol
A Automatic Fire Detectors LSN improved version en | Abbreviations ABS AcrylonitrileButadieneStyrene DIBt Deutsches Institut für Bautechnik (German Institute for Technology) DIN German Institute for Standardization DO Dual-optical DOT Dual-optical and thermal DOTC Dual-optical, thermal and chemical EN European Standard Convention Conventional technology al LED Light Emitting Diode LSN Local Security Network PI Product Information PP Polypropylene UEZ Universelle Europazentrale