Data Sheet

Certifications and approvals
Region Certification
USA UL UROX Smoke-automatic Fire Detectors
(ANSI/UL 268)
CSFM see our website
Installation/configuration notes
Compatible Products
The following products are compatible with the
FAH‑440 Analog Heat Detector:
Category Product ID Product Description
Fire Panels FPA‑1000
Series
Analog Addressable Fire Panels
Fire Panel
Accessories
FPE‑1000‑SLC Signaling Line Circuit Plug‑in
Module
Detector Bases FAA‑440‑B4 4‑inch Analog Standard Base
FAA‑440‑B6 6‑inch Analog Standard Base
FAA-440-B4-
ISO
4‑inch Analog Isolator Base
FAA-440-B6-
ISO
6‑inch Analog Isolator Base
Mounting Considerations
Detectors are typically mounted on the ceiling.
However, if detectors are mounted on a wall, they
must be at least 4 in. (10.2 cm), but no more than
12 in. (30.5 cm), below the ceiling. When other
devices containing magnets or producing magnetic
fields (for example, loudspeakers) are present in the
area, the base must be at least 1 ft (30 cm) from these
devices to prevent unwanted activation of the test
switch.
For UL Listing requirements, the spacing between heat
detectors should be no more than 50 ft (15.24 m).
Wiring Considerations
The control panel communicates to the detectors via
the analog addressable loop (SLC), which allows the
use of standard non‑twisted, non‑shielded wiring.
The following wire gauges were tested and approved:
Wire Gauge Maximum length
18 AWG (ISO 0.75 mm
2
) 4000 ft (1200 m)
16 AWG (ISO 1.5 mm
2
) 6225 ft (1900 m)
14 AWG (ISO 2.5 mm
2
) 7200 ft (2200 m)
12 AWG (ISO 4 mm
2
) 9850 ft (3000 m)
Remote Indicator
If a remote indicator is used in the circuit, it must be
no more than 10 ft (3 m) from the base.
Parts included
Quant. Component
1 FAH-440 detector
1 Dust cover
Technical specifications
Electrical
Maximum current consumption detector head at 77°F (25°C) and 39 V
bus voltage
Alarm: 5 mA
Standby: 0.17 mA
When polled: 22 mA ± 20%
Operating voltage (SLC loop): 24 VDC to 41 VDC
Maximum allowable line
resistance:
50 Ω
Environmental
Protection category: IP 42
Relative Humidity: < 95% (non‑condensing)
Temperatures
Installation: +32°F to +100°F (0°C to +38°C)
If the sensitivity temperature is programmed
within a range of +175°F to +249°F (+79.4°C
to +120.6°C), the maximum installation
temperature is +150°F (+66°C).
Storage: -13°F to +176°F (-25°C to +80°C)
Mechanical
Dimensions
Detector: 4.4 in. x 2.0 in. (11.2 cm x 5.1 cm)
Detector in 4-inch
base:
5.0 in. x 2.5 in. (12.7 cm x 6.4 cm)
Detector in 6-inch
base:
7.0 in. x 2.5 in. (17.8 cm x 6.4 cm)
Housing Material: CYCOLOY/ABS
Sensor
Airflow: 4000 ft/min (20 m/s) maximum
Sensitivity: +135°F to +194°F (+57°C to +90°C),
programmable + RoR
Trademarks
All hardware and software product names used in this
document are likely to be registered trademarks and
must be treated accordingly.
2
| FAH-440 Analog Heat Detector