Technical data

44
• DOK-DIAX02-DDC01******-PRJ1-EN-E1,44 • 01.97
4. Mounting the DDC 1.2
4.4. Minimum Clearances
During installation, make sure that the air outlet is not obstructed and the bend
radii of the cables are maintained.
Minimum clearance equals allowance for power connectors plus bend radius,
but not smaller than 300 mm.
Bend radii of
INDRAMAT cables
Type
INK 250
INK 202
INK 203
INK 204
INK 205
INK 206
INK 207
INK 650
INK 602
INK 603
INK 604
INK 605
INK 606
INK 607
Power
core
diameter
(mm
2
)
1.5
2.5
4.0
6.0
10.0
16.0
25.0
1.5
2.5
4.0
6.0
10.0
16.0
25.0
Power
cable
diameter
(mm)
11.4 ± 0.4
17.6 +0.3/-0.5
18.6 ± 0.5
20 ± 0.5
25.4 ± 0.5
26.6 ± 0.5
30.6 ± 0.7
12.2 ± 0.4
14.8 ± 0.5
16.9 ± 0.5
18.8 ± 0.6
23.8 ± 0.5
28.2 ± 0.6
29.5 ± 0.6
Minimum Bend Radius
fixed routing flexible routing
1)
(mm) (mm)
70
120
120
120
200
220
240
80
85
110
120
150
160
190
110
200
270
300
380
390
430
120
140
180
195
240
280
290
1)
Service life greater than 500 000 bend loads.
Fig. 4.4: Bend radii of INDRAMAT cables