Technical data

38
• DOK-DIAX02-DDC01******-PRJ1-EN-E1,44 • 01.97
3. Electrical Connections - Installation Guidelines
Mains contactor picked
up
Zero potential contact - Connector X8/3-X8/4
Maximum load: DC 24V/10A
AC 230V/6A
It can be queried at output power ON whether the mains contactor has been
switched on. The closed contact can be used as a condition for the drive
enable signal.
Zero potential contact - Connector X8/1-X8/2
Maximum load: DC 24V/10A
AC 230V/6A
It can be queried at output OFF whether the mains contactor has dropped out.
This information can, for example, be used as a condition to release the door
locking device.
For diagnostics purposes, drive data can be output at analog outputs AK1 and
AK2. Which drive quantities are output is determined at commissioning.
Output voltage: ± 10 V
Load capacity: 4 mA
3.18. Signal Voltages
It is possible to tap off ± 15V and +24V at connector X8. These connections
are specifically used for measuring and test purposes. Should these voltages
be applied outside of the DDC, then no interference voltages may be coupled
in (short and shielded supply lines).
Operating state contactor dropped contactor picked up
Output Power ON open closed
Operating state contactor dropped contactor picked up
Output Power OFF closed open
Mains contactor
dropped out
Analog diagnoses
outputs AK1 and AK2
X8/21 +15VM measuring voltage max.100mA
X8/22 0VM reference potential
measuring voltage
X8/23 -15VM measuring voltage max.100mA
X8/24 +24VL load voltage max.100mA
X8/25 0VL reference potential
+24VL
X8/26 ground shield
The signal voltage outputs are short-circuit proof. Maximum load
should not be exceeded, otherwise the drive could be damaged.