Technical data
24
• DOK-DIAX02-DDC01******-PRJ1-EN-E1,44 • 01.97
3. Electrical Connections - Installation Guidelines
Motor power cable
capacity
The following recommended cable types and cross sections are based on the
current load capacity listed per EN 60 204 (VDE 0113) – E mode of installation.
If other standards are required for the actual application, or if cables are routed
to accomodate a different installation mode, then greater cable cross sections
may be needed.
Current load as per EN 60 204
cross sections in A
in mm
2
Installation Installation Installation Installation
mode B1 mode B2 mode C mode E
1.5 13.5 12.2 15.2 16.1
2.5 18.3 16.5 21 22
4 25232830
6 32293637
10 44 40 50 52
16 60 53 66 70
25 77 67 84 88
leads in protective pipes and installation channels
cables and leads in protective pipes and installation channels
cables and leads on walls and on cable flat beds
MZINSTART
B1
B2
CE
Fig. 3.9: Modes of installation as per EN 60204