Technical data

18
• DOK-DIAX02-DDC01******-PRJ1-EN-E1,44 • 01.97
Cross section of the
DDC 1 connecting
cable
threephase connection
I
L
= current in connecting lead indicated in A
S
AN
= connected load indicated in VA
Recommended cable
for three-phase
connections
Calculate the current in the connecting cable to determine cable cross section.
The applicable guidelines must be followed when determining cable cross
sections.
If fuses are placed on the input side only when transformers are used, then
protect the secondary line against short-circuiting.
Ready-made INDRAMAT cables are available as connecting cables for the
DDC 1.2 The recommended cable types and cross sections apply where
INDRAMAT transformers and fuses are used.
The cable recommended in the following table has a current capacity as per
EN 60 204 (VDE 0113) – E mode of installation.
3. Electrical Connections - Installation Guidelines
I
L
=
S
AN
3 · 230V
Transf.-
Recommended secondary Recommended secondary
Drive (conn.) Connector
cable with INDRAMAT cable with INDRAMAT
controllers load on drive
autotransformers isolating transformers
in kVA
individual ready- individual ready-
parts made parts made
2 and 2.5 INS 108/02 INK 250 (1.5mm
2
) IKL 234 INK 202 (2.5mm
2
) IKL 241
DDC 1.2-N050C
3.5 and 4 INS 108/02 INK 250 (1.5mm
2
) IKL 234 INK 204 (6mm
2
) request
5 INS 108/02 INK 250 (1.5mm
2
) IKL 234 INK 202 (2.5mm
2
) IKL 241
7.5 INS 108/03 INK 202 (2.5mm
2
) IKL 241 INK 202 (2.5mm
2
) IKL 241
2 and 2.5 INS 172/25 INK 202 (2.5mm
2
) IKL 232 INK 202 (2.5mm
2
) IKL 232
3.5 and 4 INS 172/25 INK 202 (2.5mm
2
) IKL 232 INK 204 (6mm
2
) IKL 243
5 and 7.5 INS 172/25 INK 202 (2.5mm
2
) IKL 232 INK 202 (2.5mm
2
) IKL 232
DDC 1.2-N...A 10 INS 172/25 INK 203 (4mm
2
) IKL 242 INK 203(4mm
2
) IKL 242
12.5 INS 172/06 INK 204 (6mm
2
) IKL 243 INK 204 (6mm
2
) IKL 243
15.18 and 20 INS 172/10 INK 205 (10mm
2
) IKL 244 INK 205 (10mm
2
) IKL 244
25 INS 172/16 INK 206 (16mm
2
) IKL 245 INK 206 (16mm
2
) IKL 245
Recommended cable
for the DDC 1
connecting cable