Data Sheet

Magnetic Test Feature
Test the detector's operation by placing the SMK-TM
Test Magnet next to the detector's LED for three
consecutive flashes. This causes the detector to send
an alarm.
Certifications and approvals
Region Certification
USA UL UROX: Smoke-automatic Fire Detectors
(ANSI/UL 268) and UROX7: Smoke-au-
tomatic Fire Detectors Certified for Can-
ada (CAN/ULC-S529)
FM D7050 Family
CSFM see our website
FDNY-
CoA
#6173
Hong Kong HKFSD
Installation/configuration notes
Compatible Products
The following products are compatible with the D7050
Smoke Detector and the D7050TH Smoke Heat
Detector:
Category Product ID Product Description
Control Panels FPD‑7024 FACP
D7024 FACP
D7024-EXP FACP for export
G Series D9412G (or later), D7412G (or
later), and D7212G
1
(or later)
Detector Bases D7050-B6 Two-wire base
Remote
Annunciators
DRA-12/24 12/24 VDC remote annunciator
Interface
Modules
D8125MUX Multiplex bus interface module
1
The D7212G models are not UL Listed for commercial fire.
Parts included
Quant. Component
1 Detector head
1 Literature pack
Technical specifications
Environmental Considerations
Radio Frequency
Interference (RFI)
Immunity:
No alarm or setup on critical frequencies in
the range of 26 MHz to 950 MHz for field
strengths less than 50 V/m
Temperature
(normal operating):
+32°F to +100°F (0°C to +38°C)
Note: The environment where these detectors are installed must be
within the specified normal operating temperature limits.
Mechanical Properties
Color: Off-white
Dimensions
(diameter x D):
4 in. x 1.3 in. (10.2 cm x 3.3 cm)
Material: High-impact, fire-retardant ABS plastic
Power Requirements
Current (alarm): 0.55 mA maximum
Current (standby): 0.55 mA nominal
Power-up Time: 22 sec maximum
Voltage (minimum): 8 VDC peak from the multiplex bus
Ordering information
D7050 Addressable Photoelectric Smoke Detector Head
The D7050 detects large smoke particles by scattering
light from a pulsed infrared source operating with a
gated, high-speed, photodiode infrared sensor. The
symmetry of the optical chamber allows 360° uniform
smoke entry, but minimizes external light entry.
Order number D7050
D7050TH Addressable Photoelectric Smoke and Heat
Detector Head
The D7050TH, in addition to an optical smoke
chamber, has an added 135°F (57°C) fixed-
temperature sensor that expands its application to
confined areas where a fire increases air temperature
slowly and where there is a substantial increase in air
temperature before the fire breaks confinement.
Order number D7050TH
Accessories
DRA‑12/24 Remote Annunciator (12/24 VDC)
Designed to provide remote annunciation of alarms
when connected to the D7050‑B6 Multiplex Detector
Base
Order number DRA-12/24
DT‑2 Detector Removal Tool
Use the DT‑2 to remove, replace, or test the detector
head
Order number DT-2
2 | D7050 Addressable Photoelectric Smoke and Smoke Heat Detector Heads