Data Sheet
Intrusion Alarm Systems | D130 Auxiliary Relay Module
D130 Auxiliary Relay Module
www.boschsecurity.com
u 12 VDC or 24 VDC relay
u Allows switching of current or voltage
u Two non-latching Form C dry contact outputs
u Red LED shows coil is energized
u Mounts in control panel enclosure
The D130 Auxiliary Relay Module can be used with all
Bosch Security Systems control panels. The relay
module consists of a 12 VDC or 24 VDC relay. This
device allows the system to handle larger amounts of
current or different voltages that are beyond the
control panel's auxiliary power rating, or the rating of
modules such as the D8129 OctoRelay.
Notice
A UL Listed, 12 VDC or 24 VDC auxiliary power
supply is required to supply power to the D130's
coil.
The relay is polarized and has two sets of non-latching
Form C contacts. When the contacts are in the inactive
state, the normally-closed terminal has continuity with
the common terminal. When the contacts are in the
active state, the normally-open terminal has continuity
with the common terminal. The relay is activated by
switching polarity. A red LED lights to indicate the coil
is energized.
System overview
Initiating Circuit Application
The D130 is commonly used with a D125B Dual Class
B Initiating Module and a UL Listed 24 VDC power
supply. In this configuration power to the detectors
can be interrupted by a command from the fire alarm
control panel (FACP).
Certifications and approvals
Region Certification
USA UL APOU: Proprietary Alarm Units
(UL1076), UOJZ: Control Units, System
(UL864, 9th edition)
FM
CSFM see our website
FDNY-
CoA
#6174 UL 864 9th Edition
FDNY-
CoA
6059 [D9412GV3 & D7412GV3]
NYC-
MEA
12-92-E, Vol. 12 12-92-E, Vol. 12