Specifications
ISW-D8125CW-V2 | Installation and Operation Guide | Operation
14 Bosch Security Systems, Inc. | 8/11 | F01U161691-05
3.9.7 Clearing the EEPROM
Clearing the EEPROM erases the entire
point database and resets the commercial
wireless interface module to the factory
default settings. Ensure that you have a
printed copy of the programming settings
so you can manually restore them after
clearing the EEPROM.
If the data in the commercial wireless interface module
has become corrupted and you need to reprogram the
commercial wireless interface module, you need to first
clear the EEPROM.
1. From the main menu (Figure 15 on page 11),
press [3]. The keypad shows the following series of
messages:
Clearing EEPROM erases all info!
Push ENT to clear EEPROM.
Push ESC to exit.
Push ENT again to confirm.
2. Press the [ENT] key twice to erase the EEPROM.
3.9.8 Setting the RF System Supervision Interval
The RF System Supervision Interval determines how
long the commercial wireless interface module waits to
hear at least one check-in transmission (or any
transmission) from a transmitter before sending a
Missing event to the Control Panel.
The interval value that is chosen applies to
all burg point type transmitters system wide.
The supervision interval for fire points
remains fixed at 4 hours.
To set the RF System Supervision Interval:
1. From the main menu (Figure 15 on page 11),
press [5].
2. Select one of the available options:
- No supervision (Press [1] + [ENT])
- 4 hours (Press [2] + [ENT])
- 12 hours (Press [3] + [ENT])
- 24 hours (Press [4] + [ENT])
3. The keypad displays the new supervision interval
setting for two seconds.
3.9.9 RF Diagnostics
RF Diagnostics allows you to troubleshoot individual
RF transmitters programmed in the system. This menu
is split into two sub-menus: Individual point status and
Off-Normal point status.
To access the RF Diagnostics menu:
1. Press the [DIAG] key when the keypad shows an
idle text display (Figure 10, Figure 11 or Figure 12)
2. Enter a valid passcode and press [ENT].
The keypad displays the RF Diagnostics menu.
Figure 19: RF Diagnostics Menu
If there are any system faults, the keypad shows
the system faults first before showing the RF
Diagnostics menu.
3. To view the status of a specific RF transmitter,
press [1].
4. Enter the RF transmitter’s point number and press
[ENT].
- Zonex 1: Points 9-127 (Points 74 and 75 are
not available)
- Zonex 2: Points 129-247 (Points 194 and 195
are not available)