Installation guide
Conettix ITS-D6682-UL | Installation Guide | 2.0 Installation
4 Bosch Security Systems, Inc. | 2/09 | F01U078049-02
2.0 Installation
2.1 All Installations
Install the Conettix D6600 Communications
Receiver/Gateway according to NFPA 70, NFPA 72,
and the local authority having jurisdiction (AHJ).
The ITS-D6682-UL is suitable for Central Station
Protective Signaling when it is installed and used in
compliance with NFPA 72 and ANSI/NFPA 70.
Installation limits for digital alarm communicator
receivers (DACR) are under the jurisdiction of the
local AHJ.
The equipment between Ethernet Interface Modules
and the ITS-D6682-UL must be UL Listed Information
Technology Equipment (ITE).
To comply with UL, ensure the following requirements
are met:
• Mount the ITS-D6682-UL, the ITE network
interface equipment, and the D6600 that it is
connected to, in a standard 19-in rack.
• Connect the ITS-D6682-UL to an electrical outlet
located inside the same rack with the D6682 and
D6600.
• Install the ITS-D6682-UL in the same rack as the
D6600 and within 6 m (20 ft) of the D6600.
• The Ethernet and RS-232 serial cables cannot
exceed 6 m (20 ft) in length.
• Use an uninterrupted power supply (UPS) is
when the ITS-D6682-UL is used for UL Fire
(UL1481) Protective Signaling Systems.
• Use the supplied transformer (Group West/Part
number - 48D-12-900)
2.2 Mounting the D6682
Mount the D6682 on a rail or other user-supplied spot
behind the D6600 that it will be connected to. Refer to
Figure 3.
2.3 Connecting the D6682
Connect the D6682 as follows:
• Power cable to an available electrical outlet
• Ethernet cable to network switch
• RS-232 serial cable to Serial 1 port
Refer to the D6600/D6100i System Guide
(P/N: 4998122712) for applications using both
serial ports.
Refer to Figure 3.
Figure 3: D6682 Connections
1– Power cable
2– Ethernet cable
3– RS-232 serial cable (Serial 1 port)
4– Serial 2 port (empty)
5 – Standard 19-in. mounting rack