User manual
Table Of Contents
- Index
- 1 Key to symbols and safety instructions
- 1.1 Key to symbols
- 1.2 Safety information
- 2 Standard delivery
- 3 Appliance details
- 4 Installation instructions
- 4.1 Tools required
- 4.2 Location requirements
- 4.3 Secure the appliance
- 4.4 Water piping
- 4.4.1 Inlet - Outlet connections
- 4.4.2 Dielectric joint (not supplied with the appliance)
- 4.4.3 Condensate Drain Tubes (not supplied with the appliance)
- 4.4.4 TPR Valve (supplied with the appliance)
- 4.4.5 Thermal expansion tank (not supplied with the appliance)
- 4.4.6 Temperature mixing device (not supplied with the appliance)
- 4.4.7 Pressure limiting valve (not supplied with the appliance)
- 4.4.8 Expansion control valve (not supplied with the appliance)
- 4.5 Electric requirements
- 4.6 Installation configurations
- 4.7 Insulation blanket
- 4.8 Fill the water storage tank
- 4.9 Installation checklist
- 4.10 What to expect for “normal startup”
- 4.11 Off-peak compatibility
- 5 Operation Instructions
- 5.1 Safety warnings
- 5.2 Working display
- 5.3 Working modes
- 5.4 „Operating“ menu
- 5.5 Temperature set point
- 5.6 „Main“ menu
- Accessing the „Main“ menu
- 5.6.1 „Mode“ function - heating modes
- 5.6.2 „Prog“ function - Timetable operation programming
- 5.6.3 Silent Mode programming - „Sil“ function
- 5.6.4 „Leg“ function - automatic thermal disinfection
- 5.6.5 „Set“ function - adjustments
- 5.6.6 „Purg“ function - purge
- 5.6.7 „Info“ function - information
- 5.7 Troubleshooting
- 5.8 Factory configurations
- 5.9 Selecting the temperature units - „C“ or „F“
- 5.10 Setting the time and day of the week
- 5.11 Controls
- 6 Maintenance and repair
- 6.1 Periodic Inspection
- 6.2 Temperature and pressure relief valve (PTR Valve)
- 6.3 Flushing tank
- 6.4 Draining the Water Heater
- 6.5 Vacation and Extended Shutdown
- 6.6 Clearing the Condensation Drain Tubes
- 6.7 Refrigerant circuit
- 6.8 Anode Rod servicing
- 6.9 Checking/replacing the magnesium anode
- 6.10 Service menu
- 7 Display
- 8 Electrical diagram
- 9 Environmental protection
- 10 Warranty details

6 720 801 244 (2013/08)Compress 3000 DW FO
Installation instructions | 21
▶ Open the purge screw of the circulation pump and leave it
opened until the water leaks uniformly without visible air
bubbles.
Fig. 14 Circulation pump purge screw
▶ Close the circulation pump purge screw.
▶ Wait for about 5 minutes until „Purg“ mode goes off.
▶ Rotate circulation pump speed selector to position „I“.
Filling procedure is now completed.
If, after a few minutes of operation (up to 20-30 minutes),
display shows „E09“,you should:
▶ Reset the appliance ( page 32, paragraph „Resetting the
system“).
▶ Rotate circulation pump speed selector to position „III“.
▶Activate „Purg“ function ( page 31, section 5.6.6).
▶ Reopen the purge screw of the circulation pump and leave
it opened until the water leaks uniformly without visible air
bubbles.
▶ Close the circulation pump purge screw.
▶ Reopen the purge valve for a few seconds several times
during the "Purg" procedure to ensure the complete purge
of the system.
▶ After "Purg" function ends, rotate the circulation pump
speed selector to position „I“.
4.8.1 Water characteristics
Usage of water with unsuitable characteristics can result in
shortened product life.
Fig. 15 Water treatment vs water characteristics
Please note that the Langelier saturation Index depends on the
water temperature and the above information considers two
extremes: 10 °C and 70 °C.
While corrosion is higher at low water temperature, scaling is
more important at higher water temperature.
In case of water hardness above 600 mg/l, the Langelier
saturation index must be determined to evaluate the necessity
for water treatment.
Please require help from your technical assistance.
4.9 Installation checklist
1. Tank location
• Is the room size less than 3 m x 3 m x 2,5 m (22,5 m
3
)?
If yes, louvered door or similar ventilation is needed.
• Back of unit away from wall by 150 mm.
• Front of unit is free and clear.
• Is the water heater level? If not, adjust the adjustable feet,
or add shims under the base of the unit.
• Are fixing straps (if required) in place?
2. Plumbing connections
• No leaks after filling the tank with water, either when water
is flowing or is stationary.
During the 5min the Purg function lasts,
open the purge valve for a few seconds
several times. This will release some air
excess from the water loop.
6720801244-19.1V
Water conductivity for sacrificial anodes
130 μS/cm - 1500 μS/cm
Table 3 Water conductivity
Enamelled tanks must not be used with
completely desalted, distilled or de-ionised
potable water.










