Caution!
Remove all power (AC and battery) before making any
connections. Failure to do so might result in personal injury
and/or equipment damage.
Install the module
1. Set the module address using the address switches before
you install it in the enclosure.
2. Insert the plastic mounting clips onto the appropriate
standoff locations inside the enclosure or on a mounting
skirt, when required.
3. Mount the module onto the plastic mounting clips and then
secure it using the supplied mounting screws.
Wire to earth ground
To help prevent damage from electrostatic charges or other
transient electrical surges, connect the system to earth ground
before making other connections. Recommended earth ground
references are a grounding rod or a cold water pipe. When
grounding, run wire as close as possible to grounding device.
!
Caution!
Do not use telephone or electrical ground for the earth ground
connection. Use 14 AWG (1.8 mm) to 16 AWG (1.5 mm) wire
when making the connection.
24 en | Power supply Control Panels