AMC2 4W APC-AMC2-4W | APC-AMC2-4WCF | APC-AMC2-4WUS en Installation manual
AMC2 4W | en 3 Remarks This hardware is part of a security system. Access shall be limited to authorized persons only. Some states do not allow the exclusion or limitation of implied warranties, or limitation of liability for incidental or consequential damages, so the above limitation or exclusion might not apply to you. Bosch Security Systems retains all rights not expressly granted. Nothing in this license constitutes a waiver of Bosch’s rights under the U.S.
en | AMC2 4W Table of Contents 1 Please read carefully 7 1.1 Explanation of Used Symbols 7 1.2 Internet 7 2 Safety Instructions 8 2.1 Important Safety Notes 8 2.2 FCC & ICES Information 10 2.3 Safety Precautions 11 2.4 Unpacking 12 3 Introduction 13 3.1 Description of the AMC2 4W 13 3.2 Equipment Configuration 15 3.3 Performance Characteristics 18 3.4 System Overview 19 4 Technical Data 20 5 Installing 22 5.1 Mounting 22 5.2 Demounting 23 5.
AMC2 4W | en 5 5.9 RS-485 Extension Module Bus 5.10 Wiegand Interface for Card Readers 39 39 5.11 Connecting Relay Outputs 41 5.12 Connecting Analog Input Devices 44 5.13 Tamper Protection 46 6 Operating 48 6.1 Status Display of the AMC2 4W 48 6.2 Configuring the Ethernet Interface 50 6.3 Resetting the AMC2 4W 50 6.3.1 Resetting the Software 50 6.3.2 Resetting the Network Configurations 51 7 Appendix 53 7.1 Connecting Diagrams 53 7.
en | F.01U.024.965 | V.4 | 2006.
AMC2 4W Please read carefully | en 1 Please read carefully 1.1 Explanation of Used Symbols 7 Throughout this document, helpful tips, important notes, cautions and warnings will be presented for the reader to keep in mind. These appear different from the rest of the text as follows: ! CAUTION! or WARNING! These warn the operator that damage to the program or equipment might occur. NOTE! i 1.2 Important Notes – must be followed for successful operation and programming.
en | Safety Instructions AMC2 4W 2 Safety Instructions 2.1 Important Safety Notes 1. Read, Follow, and Retain Instructions - All safety and operating instructions must be read and followed properly before putting the unit into operation. Retain instructions for future reference. 2. Consider all Warnings - Adhere to all warnings on the unit and in the operating instructions. 3. Accessories - Use only accessories recommended by the manufacturer or those sold with the product.
AMC2 4W Safety Instructions | en • • 9 If the unit has been dropped or the cabinet damaged. If the unit exhibits a distinct change in performance, this indicates that service is needed. 7. Replacement Parts - When replacement parts are required, the service technician shall use replacement parts that are specified by the manufacturer. Unauthorized substitutions may result in fire, electrical shock or other hazards. 8.
en | Safety Instructions 2.2 AMC2 4W FCC & ICES Information This device complies with part 15 of the FCC rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC rules.
AMC2 4W 2.3 Safety Instructions | en 11 Safety Precautions Read instructions! ! Before working with the AMC2 4W, read these instructions carefully. Make sure you have understood all information described in this document. Warning! Risk of electric shock! ! External power supplies must be installed and put into service by qualified personnel. Compliance with the relevant regulations must be ensured.
en | Safety Instructions ! AMC2 4W CAUTION! Disconnect both AC and battery power supply before working on the controller. Warning! Risk of damage! ! Protect the hardware from electrostatic discharge by observing ESD instructions before unpacking or touching connectors or electronics. CAUTION: Lithium Battery ! Danger of explosion if battery is replaced incorrectly. Replace only with the same type as recommended by the manufacturer.
AMC2 4W Introduction | en 13 3 Introduction 3.1 Description of the AMC2 4W The AMC2 4W is equipped with four independent interfaces for Wiegand type readers. By that it is able to control two doors with a reader in each direction and up to four doors with a reader in one direction only. Fig. 3.1 The Access Modular Controller AMC2 4W All necessary information for access verification is stored in a battery buffered on-board memory and a Compact Flash (CF) memory card.
en | Introduction Fig. 3.2 AMC2 4W The AMC2 4W in a four door safety lock The AMC2 4W can communicate upstream to the host computer via eight RS-485 multi-dropped, RS-232 or 10/100 Mbit/s Ethernet. It has eight analog input devices and eight relay outputs. With its analog input devices, the AMC2 4W verifies, for example, if a lock is closed or open.
AMC2 4W 3.2 Introduction | en 15 Equipment Configuration Fig. 3.3 Upper circuit board with display (top side) 1. Internal tamper contact 2. DIL switch for RS-485 address selection, protocol and RS232/RS-485 selection 3. Lithium battery for buffering of static RAM and real time clock (RTC). The battery shall be replaced by qualified personnel every ten years or if indicated by an appropriate event. 4. Reset push button - available by using the srew driver 5. LC Display 6.
en | Introduction AMC2 4W 11. Configurable RS-232 host interface (ribbon cable connector) 12. Configurable 10/100 Mbit/s Ethernet interface Fig. 3.4 Overview - Interfaces 13. RS-485 extension module bus (Pluggable screw connector) 14. External tamper contact (Pluggable screw connector) 15. Power supply (Pluggable screw connector) 16. Wiegand interfaces for up to 4 card readers (Pluggable screw connector) 17. Connectors for eight analog inputs (Pluggable screw connector) 18.
AMC2 4W Introduction | en 17 Fig. 3.5 Jumper at the bottom side 19. Jumper: Selector for either potential free relay output or powered by AMC2 4W internal power supply (wet/dry contacts). 20. Jumper: Potential equalization between different mass systems and protective earth (shield)for the extension interface. Bosch Security Systems Installation manual F.01U.024.965 | V.4 | 2006.
en | Introduction 3.3 AMC2 4W Performance Characteristics – Intelligent access manager for 1 ... 4 entrances (e.g.
AMC2 4W 3.4 Introduction | en 19 System Overview The Access Controller AMC2 4W is connected between the management host system and different peripheral devices. By default a management host system is connected via Ethernet. A management host connection via RS-485 or RS-232 is also possible. Fig. 3.6 System overview The number of controllers in one system is limited to 200. Corresponding to the available interfaces one AMC can be connected to each COM-Port using RS-232 mode.
en | Technical Data 4 AMC2 4W Technical Data Hardware – Integrated Microcontroller (32Bit, 30MHz) – SRAM (256MB) – Serial EEPROM – RTC – Pluggable Compact Flash from 64 MB up to 1024 MB – Battery for SRAM and real time clock (RTC) – Host address selectable via DIL sliding switch or software – Host interface • RS-485 2-wire or 4-wire Transfer rate: 38,4 kBit/s (No parity, 8 Bit, 1 Stopbit) • RS-232 Transfer rate: 38,4 kBit/s (No parity, 8 Bit, 1 Stopbit) • – Ethernet 10/100 Mbit/s
AMC2 4W Technical Data | en 21 Power con- AMC: 5VA sumption Peripheral devices: using the AMC PBC-60 – up to 55VA – constant load: 25VA Connectors Pluggable screw connectors Protection IP30 Class Environment 0°C to 45°C temperature Humidity Up to 95%, without condensation Housing mate- ABS with OC (UL 94 V-0) rial Dimensions (W/H/D) 232mm x 90mm x 63mm (8.9 x 3.5 x 2.4 in.) Weight ! app. 0,53 kg (0.
en | Installing AMC2 4W 5 Installing 5.1 Mounting The AMC2 4W can be attached on a standard 35 mm (1.377 in.) mounting rail via a snap-in mechanism. Attach the AMC2 4W into the upper edge of the mounting rail, then push down the AMC2 4W and snap it onto the rail by pushing it towards the back. Fig. 5.1 Mounting the AMC2 4W on a mounting rail F.01U.024.965 | V.4 | 2006.
AMC2 4W 5.2 Installing | en 23 Demounting i NOTE! To remove the AMC2 4W from a mounting rail, first, remove all pluggable screw connectors. Push down the AMC2 4W until it snaps out of the mounting rail. Pull the lower end of the AMC2 4W from the mounting rail. Fig. 5.2 Bosch Security Systems Demounting the AMC2 4W from a mounting rail Installation manual F.01U.024.965 | V.4 | 2006.
en | Installing 5.3 AMC2 4W Opening the AMC2 4W Case i NOTE! To open the AMC2 4W, first, remove all pluggable screw connectors at least the host connection. The AMC2 4W case consists of a top cover mounted with a twopoint snap-in closure on a ground chassis. To open the AMC2 4W push down the two snap-ins with a srew driver. After that the cover can be moved to bottom. Fig. 5.3 Opening the AMC2 4W case F.01U.024.965 | V.4 | 2006.
AMC2 4W 5.4 Installing | en 25 Cabling CAUTION! The cables used in the AMC2 4W access control system are not ! prone to electrical interference. However, you should avoid routing cables close to heavy load switching cables and equipment. If this is unavoidable, cross the cable at right angles every 1 to 2 m (3 to 6 ft) to reduce interference. Grounding and Shielding The main grounding point at the AMC2 4W will be connected with pin 2 of the power supply connector - see Figure 7.6.
en | Installing AMC2 4W U = 12V, I = 1A, maximum VDrop = 2V 6,385 i.e. RAWG18 (acc. specs) = Ω 1000 ft Ω or 20,948 km Ω VDrop = 20,948 km x 0.1 km x 1A = 2.1V 6,385 VDrop = Ω 1000 ft x 328 ft x 1A = 2.1V Critical condition! Install the power supply closer to the controller. NOTE! i These specifications aim for readers, relay outputs, and extensions. For inputs there are other value to keep in mind - see therefore Table 5.3. 5.4.2 Grounding and Shielding the Host Interface Fig. 5.
AMC2 4W Installing | en 27 NOTE! Generally the following counts: – If the devices have an own power supply, the shield will be connected on one point, only. i The free end should be protected to avoid connections. – If the device will be provided by an other one, the shield have to connect on both sides. WARNING! Take care that there are no grounding loops. Setting jumper JP1 connects the internal ground of the AMC2 4W to the ground of the RS-485 host interface. Jumper JP2 manages the PAG.
en | Installing 5.4.3 AMC2 4W Grounding and Shielding the Extension Interface Fig. 5.5 Location of ground jumper bottom side Jumper B connects the internal ground of the AMC2 4W to the RS-485 ground of the slave interface. Jumper B shall only be set (B2) if the AMC2 4W powers all other peripheral devices which are directly connected to the AMC2 4W. 5.5 Connecting Power Supply Connect the power supply to the 7-pin pluggable screw connector labeled with POWER on the upper case.
AMC2 4W Installing | en 29 Fig. 5.6 Location of the power supply connector An external power supply (10 - 30V DC) must be connected for internal electronics at pin 1 (positive) and pin 3 (negative) of the pluggable screw connector. When using a shared 12V DC power supply for internal electronics and peripherals, pin 1 and pin 6 resp. pin 3 and pin 7 can be shortened.
en | Installing 5.6 AMC2 4W RS-485 Host Interface An RS-485 host system can consist of up to eight AMC2 4W controllers connected via 2- or 4-wire connection. Fig. 5.7 Configuration of a RS-485 host system F.01U.024.965 | V.4 | 2006.
AMC2 4W Installing | en 31 The following conditions apply for an RS-485 bus system: – A bus system consists of a bus line and/or one or more branch lines. – Cable lengths exceeding 100m or 300ft must be installed as bus lines. – Branch lines are branching connections from a bus line. – Peripheral devices are AMC2 4W which are connected to the host computer. – Maximum cable length of a bus line must not exceed 1200m or 4000ft.
en | Installing Fig. 5.8 5.6.1 AMC2 4W RS-485 host interface RS-485 Two Wire Connection Fig. 5.9 Connection scheme of a RS-485 two wire connection F.01U.024.965 | V.4 | 2006.
AMC2 4W Installing | en 33 Fig. 5.10 Settings for RS-485 two wire connections For RS-485 two wire connection set the AMC-MUX DIL-Switch at the position 3, 7 and 8 to ON. On the upper side of the AMC panel put the jumper on the two pins on the right hand side of the connector 8 (see also: Figure 3.3). Set the RS-485 address of the AMC using the DIL-Switch - see Section 5.6.3 DIL Switch Address Selector. 5.6.2 RS-485 Four Wire Connection Fig. 5.
en | Installing AMC2 4W Fig. 5.12 Settings for RS-485 four wire connection For RS-485 four wire connection set the AMC-MUX DIL-Switch at the position 3, 5 and 6 to ON. On the upper side of the AMC panel put the jumper on the two pins on the right hand side of the connector 8 (see also: Figure 3.3). Set the RS-485 address of the AMC using the DIL-Switch - see Section 5.6.3 DIL Switch Address Selector. i 5.6.3 NOTE! A complete connection diagram of the RS-485 host interface is shown in Figure 7.2.
AMC2 4W Installing | en 35 NOTE! Using Ethernet connection it is recommended to set switch 1 to i ON (= delivery status) Using RS-232 connection the address must be set, which is configured in the Device Editor. Therefore this is a point-to-point connection the usually configured address will be 1 - so the switch 1 must be also set to ON. Fig. 5.13 Bosch Security Systems Location of the RS-485 address selector Installation manual F.01U.024.965 | V.4 | 2006.
en | Installing AMC2 4W Address none 1 2 3 4 5 6 7 8 1 OFF ON OFF ON OFF ON OFF ON OFF DIL Switches 2 3 OFF OFF OFF OFF ON OFF ON OFF OFF ON OFF ON ON ON ON ON OFF OFF 4 OFF OFF OFF OFF OFF OFF OFF OFF ON Table 5.1 Setting the RS-485 address with the DIL switch Mode ON OFF DIL Switches 5 6 SDEB RS-232 BPA RS-485 Table 5.2 Protocol and connection settings 5.7 RS-232 Host Interface The AMC2 4W offers an RS-232 serial interface to connect a host computer or serial modem.
AMC2 4W Installing | en 37 Fig. 5.14 Location of the RS-232 serial interface The AMC is created like a PC, so you cannot build a 1:1 connection, but cross the data wires using a null modem cable for example. i 5.8 NOTE! A complete connection diagram of the RS-232 host interface is shown in Figure 7.3. Ethernet Interface The AMC2 4W offers an additional 10/100 Mbit/s Ethernet autosensing interface to connect to a local area network or host computer.
en | Installing AMC2 4W Fig. 5.15 Location of the Ethernet interface NOTE! After the connection of a new AMC in a network using DHCP it can take several time if the AMC is known on the remote server. i This cause in the DNS cache of the lokal PC - it will be refreshed only after special duration. To speed up this procedure give in the following command in a command prompt: ipconfig /flushdns After this the AMC should be available by its name.
AMC2 4W 5.9 Installing | en 39 RS-485 Extension Module Bus The RS-485 Extension Module Bus expands the AMC2 4W with additional I/O modules (AMC2 8I-8O-EXT or AMC2 16I-16OEXT). Up to three expansion modules can be connected to provide additional in- and outputs, for example, for elevator control. You can find further information about the extension boards in the installation manual of these modules (Order-no: F.01U.024.967) Fig. 5.16 i 5.
en | Installing AMC2 4W interface is connected via a 10-pin pluggable screw connector (S2, S7, S14, and S19). Fig. 5.17 Location of the Wiegand interfaces for external devices The interfaces are point-to-point connections. You can connect only one reader to an interface - the cable length is limited to 150 m (492 ft). Like the numbering of the interfaces the reader get their address. i NOTE! A complete connection diagram of the Wiegand interface is shown in Figure 7.7. F.01U.024.965 | V.4 | 2006.
AMC2 4W 5.11 Installing | en 41 Connecting Relay Outputs To operate locks or alarm systems the AMC2 4W has eight form C relay outputs. The outputs will be connected to the 3-pin pluggable screw connectors: S5, S6, S10, S11, S17, S18, S22, and S23 - see Figure 7.5. Fig. 5.18 Location of the relay output connectors Each relay output can operate in ‘wet’ mode, using the AMC2 4W's internal 12V DC power supply for external devices or ‘dry’ mode with potential free contacts for externally powered systems.
en | Installing AMC2 4W Fig. 5.19 Wet mode and dry mode of the AMC2 4W relay outputs ! WARNING! Keep in mind the following specifications. For the protection of damage the relay keep in mind, that ... – the maximum switching current is 1,25A – the maximum switching voltage is 30V DC – ohm resistive load can be connected to the relay, only – inductive loads have to be short circuited using recovery diodes - see: Figure 5.20. These diodes (BAX12A) are supplied with every AMC2 4W package.
AMC2 4W Installing | en 43 Fig. 5.20 ! i Schema of the using of the recovery diode Risk of Damage! Do not connect externally powered devices in wet mode. This can damage the AMC2 4W. NOTE! A complete connection diagram of the relay output connectors is shown in Figure 7.9. Each relay output has a separate jumper setting on the bottom side of the lower circuit board to activate wet (D2)or dry (D1) mode. Bosch Security Systems Installation manual F.01U.024.965 | V.4 | 2006.
en | Installing AMC2 4W Fig. 5.21 Location of relay output jumpers (bottom side) 5.12 Connecting Analog Input Devices The AMC2 4W has eight analog inputs, for example, for potential free lock mechanisms or to detect if a lock is closed or open. The inputs will be connected to the 2-pin pluggable screw connectors: S3, S4, S8, S9, S15, S16, S20, and S21 - see Figure 7.5. F.01U.024.965 | V.4 | 2006.
AMC2 4W Installing | en 45 Fig. 5.22 Location of the analog input connectors The AMC2 4W can also detect the wiring conditions ‘short circuit’ and ‘broken’ and initiate an alarm if the appropriate devices are connected. 1. Door open:RS + RP 2. Door closed:RS 3. Broken wire:RS + RP = 4. Short circuit:RS + RP = 0 The resistor values can vary and depend on the used lock system (wire resistance negligible). The AMC2 4W package includes 2,2 kΩ resistors using for reserves for the RS and the RP resistor. Fig.
en | Installing AMC2 4W To detect the four states there are only special values allowed for potential drop depending on the used resistors. The following table shows the values for the possible resistor combinations.
AMC2 4W Installing | en 47 Fig. 5.24 Bosch Security Systems Location of the tamper protection contact Installation manual F.01U.024.965 | V.4 | 2006.
en | Operating AMC2 4W 6 Operating 6.1 Status Display of the AMC2 4W The LC Display delivers information about the AMC2 4W status. Push the 'Dialog' button to switch between different modes. Fig. 6.1 Location of the ’Dialog’ button The display mode which has been set remains until the next operation of the ‘Dialog’ button. The order of the display pages is determined and follows the scheme shown in the table below. F.01U.024.965 | V.4 | 2006.
AMC2 4W Operating | en 49 Push 0 Display (Example) V37.02 02.03.06 Description Software versions and date of or the downloader - every 5 sec. WIEGAND alternating with the display of the reader interface. 1 (= default page) 99999876543210 A BOSCH serial number and bus address: A = address 1 ... 2 3 02.06 15:35:15 Dig.
en | Operating 6.2 AMC2 4W Configuring the Ethernet Interface To configure the AMC2 4W in a TCP/IP network environment use the tool AmcIpConfig provided in the following directory on the standalone or the remote server: \\Runtime-drive:\MgtS\AccessEngine\AC\bin This tool can be copied and used on every computer. NOTE! i 6.3 The usage of the software application to configure the AMC2 4W via Ethernet interface is described in the online help of the tool.
AMC2 4W Operating | en 51 Fig. 6.2 6.3.2 Restarting the AMC2 4W with the provided screw driver Resetting the Network Configurations 1. Reset the AMC2 4W as described above (in download program). 2. Open the upper case of the AMC2 4W as described in Section 5.3 Opening the AMC2 4W Case. 3. Set all six DIL switches of the RS-485 selector to ON 4.
en | Operating Fig. 6.3 AMC2 4W Resetting the AMC2 4W to delivery state F.01U.024.965 | V.4 | 2006.
AMC2 4W Appendix | en 53 7 Appendix 7.1 Connecting Diagrams Fig. 7.1 Connectors on upper PCB Fig. 7.2 RS-485 host on upper PCB Bosch Security Systems Installation manual F.01U.024.965 | V.4 | 2006.
en | Appendix AMC2 4W Fig. 7.3 Connecting diagram of the RS-232 serial interface Fig. 7.4 Ethernet Network socket (RJ45) F.01U.024.965 | V.4 | 2006.
AMC2 4W Appendix | en 55 Fig. 7.5 Connector blocks of the AMC2 4W Bosch Security Systems Installation manual F.01U.024.965 | V.4 | 2006.
en | Appendix AMC2 4W Fig. 7.6 Power supply Fig. 7.7 Wiegand interface Fig. 7.8 Analog input Fig. 7.9 Relay output F.01U.024.965 | V.4 | 2006.
AMC2 4W 7.2 Appendix | en 57 Fig. 7.10 Extension interface Fig. 7.11 External tamper contact Legend Twisted pair connection Transmitter Receiver Bosch Security Systems Installation manual F.01U.024.965 | V.4 | 2006.
en | Index 8 AMC2 4W Index A Address Selector 34 Analog Input Devices 44 Appendix 53 Cabling 25 Conductor data 25 Configuring the Ethernet Inter- face 50 Connecting Diagrams 53 Demounting the AMC-4 23 Description of the AMC-4 13 DIL Switch 34 Equipment Configuration 15 Ethernet Interface 37 C D E G Grounding 25 I Installing the AMC-4 22 Internet 7 L Legend 57 O Opening the AMC-4 Case 24 Operating the AMC-4 48 Performance 18 Power Supply 28 P Characteristics R Relay Outputs 41 Resett
Bosch Security Systems Robert-Koch-Straße 100 D-85521 Ottobrunn Germany Telefon 089 6290-0 Fax 089 6290-1020 www.bosch-securitysystems.