AMC2 4W Installing | en 33
Bosch Sicherheitssysteme GmbH Installation manual | V 7.6 | 2008.12
5.9 RS-485 Host Interface
An RS-485 host system can consist of up to eight AMC2
controllers connected using 2- or 4-wire connection.
Figure 5.9 Configuration of a RS-485 host system
The following conditions apply for an RS-485 bus system:
– A bus system consists of a bus line and/or one or more
branch lines.
– Cable lengths exceeding 100 m (300 ft) must be installed
as bus lines.
– Branch lines are branching connections from a bus line.
1 = Host
2 = RS-232 connection
3 = AMC-MUX - converter
4 = RS-485 bus
5 = AMC2 controller