Installation Manual

AMC2 4W Installing | en 31
Bosch Sicherheitssysteme GmbH Installation manual | V 7.6 | 2008.12
5.7 Connecting Power Supply
Connect the power supply to the POWER 7-pin pluggable screw
connector on the upper case. Refer to Table 7.3 for a complete
diagram.
Figure 5.7 Location of the power supply connector
Connect an external power supply (10 - 30 Vdc) for the AMC2
device at pin 1 (positive) and pin 3 (negative) of the pluggable
screw connector.
If an uninterruptible power supply (UPS) is used, the relay
output for power good signals from the UPS is connected to the
following pins:
pin 4 and 7 for power good AC
pin 5 and 7 for power good Battery
pin 6 and 7 for power good DC
Otherwise these pins must be short-circuited.