Specifications

IMPORTANT: By Pressing the Info button on the sensor the user can see the following
t
yp
ical data:
INFO PRESS 1 – Displays occupancy override time (in minutes)
PRESS 2 – Displays actual heating setpoint (in degrees F)
PRESS 3 – Displays actual cooling setpoint (in degrees F)
PRESS 4 – [ 1 ] - Displays discharge air temperature (in degrees F)
PRESS 5 – [ 2 ] - Displays leaving water temperature (in degrees F)
PRESS 6 – [ 3 ] - Displays active alarm code
0 Indicates NO ALARM
1 Indicates active HP alarm comp 1
2 Indicates active LP alarm comp 1
3 Indicates active HP alarm comp 2
4 Indicates active LP alarm comp 2
5 Indicates active freezestat alarm
6 Indicates active condensate alarm
7 Indicates brownout condition
20 Indicates input/out in MANUAL lock position. It is not in
AUTO
30 Indicates RS zone, discharge or leaving water
temperature sensor failure
40 Indicates high or low RS zone temperature condition
50 Indicates high or low discharge air temperature condition
60 Indicates filter or compressor service alarm
70 Indicates high or low leaving water temperature condition
PRESS 7[ 1 ] – Displays status of compressor 1 output (ON/OF)
PRESS 8 [ 2 ] – Displays status of compressor 2 output (ON/OF)
PRESS 9 [ 3 ] – Displays status of auxiliary heat output (ON/OF)
PRESS 10 Displays fan status (fan icon=fan ON), unit condition
(AU=auto)
PRESS 11 Displays unit mode (AU=auto)
PRESS 12 Goes back to default screen display
39