Specifications
5
Specifications
Power: 24VAC ± 10%, 50-60Hz, 20VA power consumption
(Single Class II 70VA or 100VA option available)
Physical: Rugged plastic housing protects circuitry.
Environmental
Operating Range: 40° to 130°F (-17.8° to 54.4°C); 10 to 90% relative humidity, non-condensing
Digital Outputs: Five binary outputs: Type A relay contacts rated at 1A resistive @ 24VAC; configured as dry
contact, normally open.
Universal Inputs: 6 to 8 universal inputs. Inputs 1 and 2 are configurable for 0-5VDC, 10K ohm thermistor, or dry
contact; inputs 3 and 4 support thermistor or dry contact only; inputs 5 and 6 support
thermistor, dry contact, or LogiStat. Inputs 7 and 8 are used for 1-10K adjustment pots or dry
contacts (FHP 583 only).
Standard
Communication: Comm. Port: 3-pin port configurable for ARC156 (BACnet-over-ARC156) or EIA-485
communications (BACnet MS/TP, Modbus RTU, or N2).
Ports: Rnet Port: 4-pin port for interface with remote mounted BACview6 or RS sensors
Local Access Port: For local communication with a laptop computer running WebCTRL or for
communication with a BACview6.
BACnet Support: Advanced Application Controller (B-AAC), as defined in BACnet 135-2001 Annex L
Communication Ports
Status Indication: Visual (LED) status of network communication, run status, errors, power, and all digital
outputs
Battery: Lithium 3V coin cell battery, CR2032, provides a minimum of 10,000 hours of data retention
(based on installation in conditioned space) during power outages.
Protection: Surge and transient protection circuitry for power and communications.
Listed by: FCC Part 15 - Subpart B - Class A. Pending listings at the time of publishing this document:
UL 916 (PAZX), cUL C22.2 No. 205-M1983 (PAZX7), CE (1997).
Weight: 0.6 Lbs. (0.27 Kg).
Overall
Dimensions
(W x H x D): 5-1/16” (129mm) x 5-11/16” (144mm) x 1-1/2” (38mm) (recommended panel depth).
Mounting Hole
Dimensions: Two mounting holes located center line of controller with 5-9/16” (141mm) vertical spacing.