The valve start command is delayed by a valve delay counter; a delay of 60 seconds is
used.
The equipment integrator must select the proper expansion module option and valve end
switch for the unit configuration.
The condenser water valve is opened by starting the compressor.
Heating & Cooling Operation
The controller will measure the zone temperature and stage the compressor(s) to maintain its
set-point. To prevent short-cycling, there will be a 5 minute delay between compressor stages (if
equipped with 2 compressors). Additionally, there will be a 1 minute delay when transitioning
between heat and cool modes. The compressor will run subject to internal safeties and controls
provided by UPM board.
Heating
Heating will be enabled whenever:
The fan output is on
The loop valve is open
The reversing valve is de-energized in heat mode.
Cooling
Cooling will be enabled whenever:
The fan output is on.
The loop valve is open
AND the reversing valve is energized in cool mode.
HGRH Start/Stop (On/Off)
Once the set-point has been satisfied and the humidity is above set-point, the unit will run until
there is another cooling call, or the humidity set-point has been satisfied. Active humidity
removal will operate the equipment until satisfied.