Specifications
19
Set-points Management
All set-points are adjustable via the network or with the BACview terminal. Adjustment Limits is
used to limit the allowed set-point changes via the wall sensor. For a given set-point the
adjustment amount is limited to ± 3 °F; this limits the upper and lower set-point adjustment
allowed by the user.
Zone Control Status Information is available via the BAS:
• Run Status – indicates the current commanded status of the unit, (on/off).
• Effective Zone Temperature – the measured space temperature with offset applied.
• Override Time – the amount of time the user has overridden the current set-point.
• Current Set-point – current set-point with limits applied.
• Effective Heating Set-point – current heating set-point with offset applied.
• Effective Cooling Set-point – current cooling set-point with offset applied.
• Night Setback Status – status indicating that the zone is:
o ON – zone is occupied
o OFF – zone is unoccupied
• Current Cooling Percent – the zone PID value for cooling operation, 0% - 100%.
• Current Heating Percent – the zone PID value for heating operation, 0% - 100%.
Zone Temperature Limits
When the RS-Sensor is selected as the primary zone sensor, a zone temperature range alarm is
asserted when the measured space temperature is above or below the following trip conditions:
• +10 degrees above cooling set-point
• +10 degrees below heating set-point
The high and low zone temperature alarm trip points may be customized via the Alarm
Configuration Screen utilizing the BACview terminal. The RS Sensor hardware is validated if
appropriately configured via the BACview terminal.
Remote Temperature Limits
When the RTS is used as the zone temperature sensor, a zone temperature range alarm is
asserted when the measured space temperature is above or below the following trip conditions:
• +10 degrees above cooling set-point