Specifications

17
Re-Heat cannot be installed in the field. Consult the humidity control section of this document
for detailed operation with HGRH.
Cooling Only with Hot Gas Re-Heat
The unit is configured for cooling only with active humidity control. Please see Heat Pump with
Hot Gas Re-Heat for additional details.
Temperature Sensor Selection
A temperature measurement is required by the DDC control software for proper unit operation
and control of space temperature.
For zone temperature applications, the temperature measurement source is user selectable for:
RS Sensor (Communicating Wall Sensor)
o RS-PRO FHP P/N: 8733800500
o RS-PLUS FHP P/N: 8733800503
o RS-BASE FHP P/N: 8733800504
Remote Temperature Sensor (10K Thermistor @25C)
o Duct Mounted RTS: 641-258
o Wall Mounted RTS: 8733800505
BAS provided value (Network Provided)
8733800504 8733800503 8733800500
Figure 12 – RS Room Sensors