Specifications

15
*
Subject to availability of IN-1 (input 1)
The LON Works protocol is supported with an option card (Figure 11). The
unit is enabled by the occupancy command, which is provided by the BAS.
Correct hardware setup of the FHP-560 and 583 is required (BAUD rate and
Communication Selection).
Manual On: Places the Heat Pump in manual run mode; the unit will operate until the set-
point is satisfied.
Override: Keeps the unit in occupied, operating mode while maintaining the occupancy
set-point, until the BAS is available for integration. For systems installations
installed with the RS walls sensor, unit operation can be overridden via the
push button located on the wall sensor. The unit will run until the occupied
set-point is satisfied or the temporary run time has expired.
Internal Control Source (Keypad)
All FHP controllers are provided with a battery backed up real time clock. When configured for
Keypad, the internal scheduler uses the local time and user schedule to initiate heat pump
operation.
Occupied Schedule
o 74°F Cooling Set-point (Adjustable)
o 70°F Heating Set-point (Adjustable)
Unoccupied Schedule
o 90°F Cooling Set-point (Adjustable)
o 55°F Heating Set-point (Adjustable)