Specifications
11
Water to Air Operation
General Description
The Heat Pump Factory mounted FHP560 or 583 controllers are factory configured with the
Water to Air application program and factory installed in the unit to be job site ready to run.
The unit will operate in a 100% stand-alone control mode or connect to a Building Automation
System (BAS) using open protocols including BACnet® (ARCNET and MS/TP), Modbus RTU,
N2 or LonWorks® (additional network interface board required for LonWorks® option). The point
mapping to all of these protocols is available in www.fhp-mfh.com and can be pre-set so that the
desired protocol and baud rates can be easily field-selected and commissioned without the need
for any additional downloads or technical assistance.
The FHP controllers also support communications for intelligent RS Room sensors and BACview
keypad/display panels.
Key Features and Benefits
• I/O point count: 5 Digital outputs, 6 Universal inputs, and 3 Analog outputs (FHP 583 only)
• Powerful high speed microprocessor with 1MB Flash memory and 1MB of battery-backed
RAM
• Built-in protocol support: BACnet® (ARCNET and MS/TP), Modbus, N2 and LonWorks®
(additional network interface board required for LonWorks® option)
• Built-in local access support: BACview6 keyboard/display and Intelligent RS Room
sensors
• On-board lithium battery holds controller time clock settings
• Program archived in non-volatile memory allows unit to be ready after long periods of
power outages.
• Parameter settings archived in non-volatile memory allows unit configuration to be
available after long periods of power outages.