FHP 560/583 USERS GUIDE 8733 806 168 641-242
Table of Contents I FHP 560/583 ................................. 1 ZONE CONTROL ................................. 18 THE ZONE CONTROLLER ...................... 4 Set-points Management .............................................. 19 Zone Temperature Limits ........................................... 19 Remote Temperature Limits ....................................... 19 SPECIFICATIONS ................................. 5 FAN MODE ......................................... 20 BATTERY REPLACEMENT ....
SEQUENCE OF OPERATION................ 38 Run Conditions: ............................................................. 38 Occupied Mode ........................................................... 38 Unoccupied Mode (night setback):.............................. 38 Auto Changeover Mode .............................................. 38 Digital Input Mode ...................................................... 39 BAS Mode ................................................................... 39 Leaving Low Temp:.
The Zone Controller The Zone control board, also known as DDC Output (AO) plug above the Binary Output (Direct Digital Controller) and shown in (BO) plug. figure 1, is used in most configure-to-order The controller is programmed from the applications. supplier or at the factory with software It is BACnet® native, which makes it flexible versions that suit the different applications and easy to integrate into existing Building FHP offers.
Specifications Power: 24VAC ± 10%, 50-60Hz, 20VA power consumption (Single Class II 70VA or 100VA option available) Physical: Rugged plastic housing protects circuitry. Environmental Operating Range: 40° to 130°F (-17.8° to 54.4°C); 10 to 90% relative humidity, non-condensing Digital Outputs: Five binary outputs: Type A relay contacts rated at 1A resistive @ 24VAC; configured as dry contact, normally open. Universal Inputs: 6 to 8 universal inputs.
Controller Hardware Features LED Indicators The DDC is equipped with three sets of LED banks that help the user diagnose problems and/or identify normal operation. The first bank of LEDs is located in the upper left-hand corner as shown in Figure 2. Figure 2 - Network LEDs The LEDs (Rx and Tx) flash repeatedly when the controller is communicating with the network. The second bank is located on the upper right hand corner of the controller as shown in Figure 3.
The third and final bank of LEDs are located at the bottom right corner of the controller, as shown in Figure 4, and indicate whether each of the five (5) Binary or Digital Outputs (BO) are energized or not. DIP and Rotary Switches Figure 5 – Controller Address Rotary DIP switch Two sets of switches can be found on the controllers; they must be set properly to I MP O R T A N T : allow correct operation of the unit.
(1) SW1 and SW2 set the baud rate of the communications port on the controller: BAUD RATE 9600 19.2K 38.4K 76.8K (2) SW3 supported and SW1 Off Off On On SW2 Off On Off On SW4 protocols enable on the BACnet® MS/TP • Thermistor • Dry Contact however, there may be cases where a different controller; SW3 SW4 Off On Off On Off Off On On particular sensor is required by the customer after it leaves the factory.
4. Use needle nose pliers to remove the old battery and insert the new one. 5. Connect network cable and verify Rx and Tx LEDs are flashing. 6. Check with BAS operator for DDC functionality 7. After the battery is replaced, if additional service on the unit is required follow OSHA standards.
LonWorks® card option LonWorks® is a network platform that allows any facility or to integrate sub-systems using a common system architecture and infrastructure. This platform provides fully open operability of the components within a system or sub-system, this enables the facility owner to utilize different vendors and still have the capability of integrating their system into one single server or front end. The LON card option is available for both controllers.
Water to Air Operation General Description The Heat Pump Factory mounted FHP560 or 583 controllers are factory configured with the Water to Air application program and factory installed in the unit to be job site ready to run. The unit will operate in a 100% stand-alone control mode or connect to a Building Automation System (BAS) using open protocols including BACnet® (ARCNET and MS/TP), Modbus RTU, N2 or LonWorks® (additional network interface board required for LonWorks® option).
Inputs • RS Room temperature sensor (Rnet) • RS Room temperature sensor Set point adjust (Rnet) • RS Room temperature sensor Occupancy override (Rnet) • Discharge air temperature sensor • Leaving water temperature sensor • Unit Protection module (UPM) Alarm codes (7 safety shutdown alarms) • Unit Filter status (optional) • Unit Enable manual control (optional DI Enable) Outputs • Unit blower control • Reversing Valve • Cooling Stage 1 • Cooling Stage 2 (Comp 2 Circuit or Comp1 Stage 2
Status • Cooling/Heating control status • Cooling/Heating percentage (0-100%) • Room temperature • Discharge air temperature • Leaving water temperature • Changeover temperature • Unit filter status (optional) • Fan-Hours runtime counter (filter replacement indicator) • Fan starts counter • Comp 1 starts counter • Comp 2 starts counter (Comp 2 Circuit) Alarms • Room temperature high/low differential • Leaving water temperature high/low trip • Discharge air temperature high/low tri
Sequence of Operation • Supported Controllers: FHP560 and FHP583. • Depending on the options selected, an Input Expansion Module may be required to support additional inputs. • A detailed points list (included in the BACview Manual) should be consulted for specific points and values. Control Source (Run Conditions) The heat pump unit may have external or internal control sources to initiate heating or cooling operation.
*Subject to availability of IN-1 (input 1) The LON Works protocol is supported with an option card (Figure 11). The unit is enabled by the occupancy command, which is provided by the BAS. Correct hardware setup of the FHP-560 and 583 is required (BAUD rate and Communication Selection). Manual On: Places the Heat Pump in manual run mode; the unit will operate until the setpoint is satisfied.
Unit Mode The Unit Mode is used to configure the heat pump per its specific design configuration and application. A unit mode may be selected from the following: • Cooling Only • Auxiliary Heating (Cooling Only + Aux Heat) • Heat Pump • Heat Pump with Aux Heat • Heat Pump with Hot Gas Re-Heat • Cooling Only with Hot Gas Re-Heat Cooling Only The unit is configured for mechanical cooling only and the reversing valve and plumbing are not installed.
Re-Heat cannot be installed in the field. Consult the humidity control section of this document for detailed operation with HGRH. Cooling Only with Hot Gas Re-Heat The unit is configured for cooling only with active humidity control. Please see Heat Pump with Hot Gas Re-Heat for additional details. Temperature Sensor Selection A temperature measurement is required by the DDC control software for proper unit operation and control of space temperature.
The following applies to the Sensors: • Only one temperature source value will be used by the control software. A RS sensor may be installed to provide temperature feedback to the occupant even if a BAS or remote sensor is installed. • A zone remote sensor may not be installed with a hardwire CO2 sensor. Option configuration must be specified and adapted as required by the application. The software will lock out the remote temperature sensor if a hardwired CO2 option is selected.
Set-points Management All set-points are adjustable via the network or with the BACview terminal. Adjustment Limits is used to limit the allowed set-point changes via the wall sensor. For a given set-point the adjustment amount is limited to ± 3 °F; this limits the upper and lower set-point adjustment allowed by the user. Zone Control Status Information is available via the BAS: • Run Status – indicates the current commanded status of the unit, (on/off).
• +10 degrees below heating set-point The high and low zone temperature alarm trip points may be customized via the Alarm Configuration Screen utilizing the BACview terminal. The remote zone sensor hardware is validated if appropriately configured/installed. Fan Mode The Fan Mode option is used to select the type of fan hardware being used with the unit. Fan hardware is application specific and it will determine the behavior for the specific application for which it is being applied.
The Fan will operate when the cooling or heating PID value is greater than 10% for zone control applications, if it is set to cycle with the compressors. For Discharge Air Control (DAC) applications, the fan input percent is acquired from the PID static pressure control logic. DAC fan operation will run only during occupancy and for the unit being configured for discharge air control. The fan may be configured for continuous operation during occupancy or for operation during compressor operation.
pressurization of the space. The speed of the fan during a smoke event is user configurable for VFD enabled units (defaults to 100%). Fan History Statistics The controller will collect fan history statistics and sum the total number of fan start events that occurred in the proceeding 1 hour period. The fan history may be reset by the user. Fan history reset may be performed locally at the unit with a BACview terminal.
Filter Status (DFS) The FHP-560/583 controller has the option of providing a filter alarm for indicating that the filter needs servicing. The filter-status service option may be implemented with hardware or with fan run time. For dedicated functionality (without expansion module), the filter switch hardware is connected directly to IN-5 with a contact closure indicating a service event and the equipment integrator must configure the dedicated filter switch option.
Differential Pressure Switch (DPS) The differential pressure switch is applied to a unit for which the flow of water through the heat exchange must be confirmed prior to the unit operating. For dedicated functionality, the differential pressure switch hardware is connected directly to IN-5 with a contact closure indicating a service event, and the DPS option must be configured by the equipment integrator.
Smoke Detector Status (SDS) The unit may be setup to receive a smoke event via a contact closure. The smoke detector input is wired to the expansion module. Consult the wiring diagram for specific wiring port location. The response to a smoke event must be determined by safety regulations and jurisdiction of the local governing body. The smoke detector response must be enabled and setup by the system integrator and safety personnel.
• The valve start command is delayed by a valve delay counter; a delay of 60 seconds is used. • The equipment integrator must select the proper expansion module option and valve end switch for the unit configuration. • The condenser water valve is opened by starting the compressor. Heating & Cooling Operation The controller will measure the zone temperature and stage the compressor(s) to maintain its set-point.
Dedicated Outside Air When in cooling mode, if the unit is equipped with modulating hot gas re-heat valve, it will be enabled and modulated to maintain supply air temperature set point, factory default is 55 °F (adj.) +/- 2°F. The cooling stages are reset with outside air temperature (OAT) as it changes as follows: Mechanical Heating 45 °F 60 °F (adj.) Mechanical Cooling Full Load OAT > 75 °F (adj.
Discharge Air Temperature (DAT) Sensor The DAT sensor is typically factory installed at the inlet of the blower housing and connected to IN-6 of the FHP-560/583 controller. For parallel coil applications it is best to locate a duct mounted sensor in the supply air stream since supply air stratification can occur during 1st stage operation. Supply duct sensor placement provides a better measurement of the discharge air temperature due to the mixing process.
Figure 13 - Typical water to air applications – Water to Air Standard (Mechanical) 29
Figure 14 -Typical water to air applications – Water to Air with Hot Gas Re-Heat (Mechanical) 30
Figure 15 - Typical water to air applications – Water to Air with Discharge Air Control (Mechanical) 31
Figure 16 - Typical water to air applications – Water to Air Standard (Electrical) 32
Figure 17 -Typical water to air applications – Water to Air with Hot Gas Re-Heat (Electrical) 33
Figure 18 - Typical water to air applications – Water to Air with Discharge Air Control (Electrical) 34
Figure 19 -Typical water to air applications – Temperature Averaging 35
Water to Water Operation General Description The Heat Pump Factory mounted I/O Zone 560 or 583 DDC Controllers are factory configured with the Water to Water application program and factory installed in the unit to be job site ready to run. The Unit will operate in a 100% stand-alone control mode or connect to a Building Automation System (BAS) using open protocols BACnet® (ARCNET and MS/TP), Modbus RTU, N2 or LonWorks® (additional network interface board required for LonWorks® option).
Control & Status Parameters and Alarms Status and Control • • • • • • • • • • • • BACview occupancy schedule System control: Schedule, Manual ON, BAS or DI Enable Load (entering) water temperature Leaving (source) water temperature Changeover temperature (optional) Cooling/Heating control status Cooling/Heating percentage (0-100%) Heating/Cooling mode manual control (optional) Reversing valve control Pump control (optional) Comp 1 control Comp 2 control (Comp 2 Circuit) Alarms • • • • • • • • • • • • Loa
Sequence of Operation Run Conditions: The unit will run according to a user definable time schedule, dry contact (physical digital input number 1), manual ON command from BACview control interface or via third party front end start command (BV software point). When commanded to run the unit will operate in the following modes: Occupied Mode: The unit will maintain • A 54°F (adj.) Cooling setpoint • A 105°F (adj.) Heating setpoint Unoccupied Mode (night setback): The unit will maintain • A 74°F (adj.
Auto Cool: • Chageover Temperature > Changeover Setpoint + Change over dead Band Auto Heat: • Chageover Temperature < Changeover Setpoint - Change over dead Band When using the changeover feature the system will require an air temperature sensor (10KΩ @ 77°F Thermistor) typically located in the controlled zone.
Lead - Lag Compressor operation NOTE: This feature is only available on two stage systems. The unit will alternate the compressors by using Lead Lag control algorithm; the rotation method is user definable and can be set during the commissioning process as follows: • Monthly • Daily • Time of Day By default the unit will change its lead compressor if the one acting as lead fails.
Load Water (Entering) Temperature: The controller will monitor the entering load water temperature which is located at entering side of coil. Alarms will be provided as follows: Load High Temp: If the water temperature at the entering load side is greater than the cooling setpoint plus a user definable amount (adj.), the factory default for this amount is 10°F. Load Low Temp: If the water temperature at the entering load side is less than the heating setpoint minus a user definable amount (adj.
Figure 20 - Typical water to water applications – Water to Water Standard (Mechanical) 42
Figure 21 - Typical water to water applications – Water to Water Standard (Electrical) 43
NOTES 44
601 N.W. 65th Court, Ft. Lauderdale, FL 33309 Phone: 866-642-3198 Fax: 954-776-5529 www.fhp-mfg.com 970-443 REV.