Specifications

96
• DOK-DIAX01-MAIN+2AD+1M-ANW1-EN-E1,44 • 07.97
3.21 Starting lockout in KDA/TDA
For safety reasons, the main spindle should be stopped when setting-
up machine tools. INDRAMAT main spindle drives are thus fitted with
a starting lockout.
The modular system's main drive remains selectively and reliably shut
down.
Disconnection is safe, even if the electronics malfunction, since the
opto-couplers are switched off and the power bridge is inhibited.
Even with defective power transistors, no rotating field can be generated
with an active starting lockout.
Note:
If the AS control input is at 0, the display shows DISABLED and the
starting lockout is activated.
If the AS control input goes from 0 to 1, the controller enabling signal must
be applied once again (RF control input goes from 0 to 1) in order to start
the drive.
3. Controller Functions
If the starting lockout is active, the READY signal output goes to 0. The
Bb potential-free contact remains closed so that the other control units
of the drive package are not shut down.
Safety note: Remove connector plug from terminal strip X2 to
ensure that the AS input is set to 0. The starting lockout (AS)
does not meet personnel safety requirements in the vicinity of
the main spindle!
Anlaufsperre-KD
A
27
23
24
25
26
28
29
30
31
32
33
34
35
36
37
4
POS 2
E-STOP (RAC only)
RF
RUN
POS 1
MD-RED
OSCILATE
PAR 1
PAR 2
LIMIT 1
LIMIT 2
LIMIT 4
SPEED 1
SPEED 2
EXT POS
READY
X2 Control inputs
control unit
3 AS ( KDA/TDA only)
X2 Signal output
0 = starting
lockout on
^
0 = drive not
ready
^
0V ext
or 0V int
+15V
+5V
message
DISABLED
to processor
control
power section
Legend:
1 = +24V
0 = 0V
= Signal step
= any control
state
^
^
^
^
6
x
Figure 97: Control inputs for starting lockout in KDA; internal circuit of controller