Specifications
73
• DOK-DIAX01-MAIN+2AD+1M-ANW1-EN-E1,44 • 07.97
3.10.2 Signal output with adjustable threshold for drive
utilization (LOAD LIMIT)
The signal threshold for drive utilization is fully adjustable. It is included
in each of the switchable parameter records PQRS and can be arranged
as torque utilization or power signal threshold.
If the drive utilization reaches the signal threshold of the active parameter
record, then the LOAD LIMIT signal output is active.
3. Controller Functions
Para-Meldeschwelle
Parameter protocol !
☞
Parameter
P19
A06
Designation
LOAD LIM
FUNCT 2
Function
signal limit for output load
signal limit is power-related,
value in LOAD LIM is kW
signal limit is torque-related,
the value in LOAD LIM is a % of peak torque
Value range or value
1 to 99
< 0 >
< 1 >
( % or kW)
S R Q
Meldeschwelle
27
23
24
25
26
28
29
30
31
32
33
34
35
36
37
3
1
1
POS 2
E-STOP (RAC only)
RF
RUN
POS 1
MD-RED
OSCILATE
PAR 1
PAR 2
LIMIT 1
LIMIT 2
LIMIT 4
SPEED 1
SPEED 2
EXT POS
AS (KDA/TDA only)
1
0
select one of the
four switchable
parameter records
(see table)
X2 control inputs
control unit
Table:
PAR 1 PAR 2
control inputs parameter
0
1
0
1
0
0
1
1
P19
Q19
R19
S19
LOAD LIM
Legend: 1 = +24V
0 = 0V
= signal step
= any control
state
^
^
^
^
control unit
13 LOAD LIMIT
X2 signal outputs
^
0 = signal
threshold
exceeded
1
Figure 64: Control inputs and signal output for adjustable signal threshold
Figure 65: Parameter for adjustable signal threshold