3. Controller Functions
Para.Drehzahlsollwertrampe
Parameter protocol !
☞
Parameter
P01
P02
P03
P04
P05
A06
Designation
RAMP 1
RPM 1
RAMP 2
RPM 2
RAMP 3
FUNCT 2
Function
ramp 1 switched off
gradient of ramp 1
end speed of ramp 1
ramp 2 switched off
gradient of ramp 2
end speed of ramp 2
ramp 3 switched off
gradient of ramp 3
the ramp set is also active
- switching EXT POS and power failure (all controllers)
- switching of E-STOP (RAC only)
Value range or value
0
1.....999
1.....24000
0
1.....999
1.....24000
0
1.....999
< 32 >
(rad / s
2
)
(1 / min
)
(rad / s
2
)
(1 / min
)
(rad / s
2
)
S R Q
S R Q
S R Q
S R Q
S R Q
If the ramps are to remain active during a change of weighting (EXT
POS), during an E-stop and mains off, this must be specified via function
parameters.
Note:
All three ramps must be set when the ramp function is used. Slopes must
be entered in rad/s
2
(see Figure 27 for conversion).
Figure 27: Parameters for speed command value ramps