3.5 Assembling the reader module
3.5.1 Configuring the reader (DIP switches)
Depending on the firmware function, the DIP switches of the reader module must be set
accordingly.
The reader has 6 DIP switches. Each switch is numbered from 1 to 6.
With the DIP switches it possible to:
Set the address of the reader
Set the BUS termination
Set baud rate for phg_crypt protocol
To change the reader configuration:
1. Power-off the reader.
2. Set the DIP switches correctly.
3. Power-on the reader.
654321
65 874321
ON WE
OSDP protocol
Address 1 2 3 4 5 6 7 8
S1 ON - ON - ON - ON -
S2 - ON ON - - ON ON -
S3 - - - ON ON ON ON -
S4 - - - - - - - ON
S5 Reserved (default - OFF)
S6 Bus terminator resistor (default - OFF)