Specification
Technical Evaluation Report (TER)
TER No. 1212-01 Page 7 of 10
Versetta Stone
®
Panelized Stone Veneer
Applications Over Continuous Insulation
Copyright © 2018
6.1.5. All other installation and flashing details germane to the project shall be in accordance with the applicable
building code and the manufacturer’s installation instructions.
6.2. Wood-Framed Walls
6.2.1. Versetta Stone
®
shall be installed over nailable structural sheathing capable of resisting 100% of the
design wind loads and shall be attached, at a minimum, in accordance with Table 1.
6.2.2. Versetta Stone
®
may be installed with (an) intervening layer(s) of continuous insulation and attached in
accordance with Table 1.
6.2.3. Each Versetta Stone
®
panel shall be installed with a minimum of four (4) fasteners as follows:
6.2.3.1. Two (2) of the fasteners must be installed into the wood stud framing and penetrate a minimum of 1"
into the framing.
6.2.3.2. The other two (2) fasteners must be installed into the nail base and must protrude out the back side of
the nail base a minimum of ½".
6.2.4. Fastener sizes shall be in accordance with Table 1 or generally accepted engineering practice.
6.3. Steel-Framed Walls
6.3.1. Versetta Stone
®
shall be installed over sheathing capable of resisting 100% of the design wind loads and
shall be attached, at a minimum, with screws in accordance with Table 1.
6.3.2. Versetta Stone
®
may be installed over (an) intervening layer(s) of continuous insulation and attached in
accordance with Table 1.
6.3.3. Each Versetta Stone
®
panel shall be installed as follows:
6.3.3.1. Two (2) fasteners must be installed into the steel stud framing and penetrate a minimum of 3 threads
into the framing (i.e., one fastener into each stud covered by the Versetta Stone
®
panel).
6.3.3.2. Two (2) fasteners must be installed into the nail base and must protrude out the back side of the nail
base a minimum of ½”. Where nailable sheathing is not used, Versetta Bridging shall be used to
transfer loads to studs.
7. Test and Engineering Substantiating Data:
7.1. Reports showing compliance with ASTM C1186 for the physical and mechanical properties of the product.
7.2. Report showing strength of nail hem bond strength.
7.3. Reports of water drainage testing in accordance with ASTM E2273.
7.4. Reports of pressure equalization testing in accordance with ASTM D3679, Annex A1.
7.5. Reports of transverse wind load testing in accordance with ASTM D5206, Procedure B.
7.6. Reports showing compliance with required quality control procedures and documentation.
7.7. Fastening Systems for Continuous Insulation, Final Report 10-11; New York State Energy Research and
Development Authority (NYSERDA); Albany, NY; April 2010.
7.8. Baker, P. and Lepage, R.; Cladding Attachment Over Thick Exterior Insulating Sheathing; Prepared by the
Building Science Corporation for the National Renewable Energy Laboratory on behalf of the U.S. Department
of Energy’s Building America Program; January 2014.
7.9. Baker, P; Initial and Long-Term Movement of Cladding Installed Over Exterior Rigid Insulation; Prepared by the
Building Science Corporation for the National Renewable Energy Laboratory on behalf of the U.S. Department
of Energy’s Building America Program; September, 2014.
7.10. The product(s) evaluated by this TER fall within the scope of one or more of the model, state or local building
codes for building construction. The testing and/or substantiating data used in this TER is limited to buildings,
structures, building elements, construction materials and civil engineering related specifically to buildings.










