Specifications
17
If either of the two loads is TEST MODE. The two loads will be TEST MODE
simultaneously.
If either of the two loads is ON/OFF MODE. The two loads will be ON/OFF
simultaneously. But there is an exception, as long as one of the loads is TEST
MODE, the TEST MODE will prevail.
·Battery Type Setting
Press Setting Switch and hold on 5 seconds when the led is on battery type setting
mode. The led will be flashing. Continue to press and the number will repeat from 1 to
3, and stop pressing until the desired number appears according to the following
setting table:
Battery Type
LED digital indicator
Sealed battery
1
Gel battery
2
Flooded battery
3
Table 4-4 Battery Type Setting
5 Protections, Troubleshooting and Maintenance
5.1 Protections
·Solar Overload
TRACER will limit battery current to the 10A maximum rating. An over-sized
solar array will not operate at peak power. The solar array should be less than the
TRACER nominal max. input power rating for optimal performance.
·Load Overload
If the load current exceeds the maximum load current rating, the TRACER will
disconnect the load. The greater the overload, the faster the load will be disconnected.
A small overload could take a few minutes to disconnect. The TRACER will attempt
to reconnect the load twice. Each attempt will be approximately 10 seconds apart.
After this, the load will remain disconnected until power is removed and reapplied.
·Solar Short Circuit
Solar input power wires are short-circuited. Charging automatically resumes
when the short is cleared.