Specifications

7
Connect load positive (+) and negative (-) to the TRACER load output as shown
in figure 3-2.
An in-line fuse holder should be wired in series in the load positive (+) or
negative (-) wire as shown. DO NOT INSERT A FUSE AT THIS TIME.
If wiring the load connection to a load distribution panel, each load circuit should
be fused separately. The total load draw should not exceed the 10A load rating.
Step 2: Battery Wiring
WARNING: Risk of explosion or fire! Never short circuit battery positive (+)
and negative (-) or cables
Figure 3-3 Battery wiring
Before connecting the battery, measure the battery voltage. It must be over 9 V to
power the controller. For 24V, the voltage must be greater than 18V to properly detect
a 24V battery. The 12/24V battery detection is automatic and the check is only
performed at start-up.
Wire an in-line fuse holder no more than 150mm from the battery positive
terminal. DO NOT INSERT FUSE AT THIS TIME.